Sanyo 85464359982001 installation instructions unit is installed 1-10.Check of Limit Density

Models: 85464359982001

1 96
Download 96 pages 22.69 Kb
Page 14
Image 14
unit is installed.

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 14

Always check the gas density WARNING limit for the room in which the

unit is installed.

1-10. Check of Limit Density

When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.

If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.3)

<Limit density 0.3 (oz/ft.3)

The limit density of refrigerant R410A which is used in this unit is 0.3 oz/ft.3 (ISO 5149).

The shipped outdoor unit comes charged with the amount of refrig- erant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)

Pay special attention to any location,

CAUTION such as a basement, etc., where leak- ing refrigerant can accumulate, since

refrigerant gas is heavier than air.

1-11. Installing Distribution Joint

(1)Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit

(APR-CHP680BA, APR-CHP1350BA, APR-P160BA, APR-P680BA, APR-P1350BA).

(2)When creating a branch using a commercially available T-joint (header joint system), orient the main tubing so that it is either horizontal (level) or vertical. In order to prevent accumu- lation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizontal. If the main tubing is verti- cal, provide a raised starting portion for each branch.

(3)If there are height differences between indoor units or if branch tubing that follows a distribution joint is connected to only 1 unit, a trap or ball valve must be added to that

distribution joint. (When adding the ball valve, locate it within 1.3 ft. of the distribution joint.)

If a trap or ball valve is not added, do not operate the sys- tem before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor.)

Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the following table.

 

ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ft.2

 

 

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1136

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1079

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9000

 

Range below

 

 

 

 

 

 

 

 

 

 

1022

 

h)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8500

 

the density limit of

 

 

 

 

 

 

 

966

 

g

 

 

 

 

 

 

 

 

 

 

 

8000

 

 

 

 

 

 

 

 

909

Min. indoor floor area

n the ceiling is 8.8 ft. hi

Min. indoor volume

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

 

7500

 

 

 

 

 

 

 

 

 

 

 

852

 

 

 

 

 

 

 

 

 

 

 

7000

 

(countermeasures

 

 

 

 

 

 

 

795

 

 

 

 

 

 

 

 

6500

 

not needed)

 

 

 

 

 

 

 

 

 

 

738

 

 

 

 

 

 

 

 

 

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

682

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

568

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

511

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

454

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

398

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

Range above

 

 

341

 

(whe

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

the density limit of

 

 

284

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

227

 

 

 

 

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

(countermeasures

 

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

needed)

 

 

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

500

1000

1500

2000

2500

3000

 

 

 

 

 

Total amount of refrigerant

 

 

oz

 

 

 

 

 

 

 

 

 

 

Tube branching methods (horizontal use)

 

 

°

 

to

30

15

 

 

 

 

 

 

 

B

 

 

 

A

Horizontal

A

B

line

View as seen

 

 

 

 

 

 

 

from arrow

 

 

Arrow view

 

 

Types of vertical trap specifications

 

(When using ball valve)

 

 

Main tubing

 

 

 

Ball valve

Indoor unit (more than 2 units)

(If only 1 unit is connected, a ball valve

(BV: purchased

separately)

is also needed on this side.)

Indoor unit (1)

 

 

 

(When not using ball valve)

 

Main tubing

Horizontal

 

 

 

 

 

 

 

 

Indoor unit (Each unit is connected

Branch tubing is

 

to tubing that is either

 

level or is directed

directed upward.

 

 

downward.)

 

 

More than

 

 

 

 

 

 

 

 

8 inch

 

 

 

 

 

 

 

 

Indoor unit is directed downward

 

 

 

14

Page 14
Image 14
Sanyo 85464359982001 installation instructions unit is installed 1-10.Check of Limit Density