CAUTION
●The indoor unit includes a drain pump. Be sure to use a level gauge and verify that the unit is level.
●Before inserting the ceiling material, complete as much of the drain piping work and refrigerant tubing work as possible.
(6)The distance between the unit and the opening of the ceiling and the distance between the bottom surface of the ceiling and the bottom surface of the flange of the unit should follow the dimensions given in Figs.
3-10. Installing the Drain Piping
(1)Prepare standard hard PVC pipe (O.D.
The PVC pipe must be purchased separately. The unit’s transparent drain port allows you to check drainage. (Fig.
CAUTION
●Do not use adhesive at the drain connection port on the indoor unit.
●Insert the drain pipe until it contacts the socket, as shown in the figure at right, then secure it tightly with the hose band.
●Tighten the hose clamps so their locking nuts face upward. (Fig.
●Do not use the supplied drain hose bent at a 90° angle. (The maximum permissible bend is 45°.)
●Check the drainage at the unit drain port (transparent).
(2)After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe, then secure it with the supplied clamps. (Fig.
NOTE
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
19/32 | |||
| |||
| Suspension bolts |
| |
| Tubing side |
| |
19/32 | Suspension bolts | Unit: in. | |
| |||
|
|
| |
| Fig. |
| |
|
| Ceiling | |
|
| material | |
25/32 | 25/32 | 25/32 |
|
| Fig. |
| |
Align the hose band with end of the |
| ||
hose, and tighten so that it does not |
| ||
contact the bead. |
|
| |
Drainage check |
|
| Hard PVC |
section on drain port | Hard PVC | pipe | |
(transparent) | Drain hose | ||
| (supplied) | socket | |
|
| (not supplied) | (not supplied) |
PVC adhesive
Bead Packing (supplied)
Fig.
Drain insulator (supplied)
Fig.
A