●Examples of the No. of indoor units settings (S005, S004)
Indoor unit setting (S005)
No. of indoor units (3P DIP switch, blue) 10 20 30
1 unit (factory setting) | ON |
|
| ON |
All OFF | 2 | 3 |
| |
| 1 | OFF | ||
| ON |
|
| ON |
11 units | 1 ON | 2 | 3 |
|
| 1 | OFF | ||
| ON |
|
| ON |
21 units | 2 ON | 2 | 3 |
|
| 1 | OFF | ||
| ON |
|
| ON |
31 units | 3 ON | 2 | 3 |
|
| 1 | OFF | ||
| ON |
|
| ON |
40 units | 1 & 3 ON | 2 | 3 |
|
| 1 | OFF |
Indoor unit setting (S004)
(Rotary switch, red)
1 Set to 1
1 Set to 1
1 Set to 1
1 Set to 1
0
Set to 0
● Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002)
System address (S003)
System address No. (2P DIP switch, blue) 10 20
| ON |
| ON |
System 1 (factory setting) | Both OFF |
|
|
| 1 | 2 | OFF |
| ON |
| ON |
System 11 | 1 ON | 2 |
|
| 1 | OFF | |
System 21 | ON |
| ON |
2 ON | 2 | OFF | |
| 1 | ||
System 30 | ON |
| ON |
1 & 2 ON | 2 |
| |
| 1 | OFF |
System address (S002) (Rotary switch, black)
1 | Set to 1 |
| |
1 | Set to 1 |
| |
1 | Set to 1 |
|
0
Set to 0
● Examples of the No. of outdoor units settings (S006)
No. of outdoor units
1 unit (factory setting)
2units
3units
4units
Outdoor unit setting (S006)
(3P DIP switch, blue)
ON |
|
| ON |
1 ON |
|
|
|
1 | 2 | 3 | OFF |
ON |
|
| ON |
2 ON |
|
|
|
1 | 2 | 3 | OFF |
ON |
|
| ON |
1 & 2 ON |
|
|
|
1 | 2 | 3 | OFF |
ON |
|
| ON |
3 ON |
|
|
|
1 | 2 | 3 | OFF |
●Address setting of main outdoor unit (S007)
Unit No. setting | Address setting of outdoor unit (S007) | |
(3P DIP switch, blue) | ||
|
Unit No. 1 (main unit) (factory setting)
ON
1 2 3
ON
OFF
●Address setting of sub outdoor unit
Unit No. setting
Unit No. 2 (sub unit) (factory setting)
Unit No. 3 (sub unit)
Address setting of outdoor unit (S007)
(3P DIP switch, blue)
ON |
|
| ON |
2 ON |
|
| OFF |
1 | 2 | 3 | |
ON |
|
| ON |
1 & 2 ON |
|
|
|
1 | 2 | 3 | OFF |
ON |
|
| ON |
Unit No. 4 (sub unit) | 3 ON |
1 2 3 | OFF |
The sub unit control PCB contains the same switches as the main unit control PCB for No. of indoor units, No. of outdoor units, and system address. However it is not necessary to set these switches.
73