Sanyo 85464359982001 Main tubing, Distribution joint tubing, Checking of limit density

Models: 85464359982001

1 96
Download 96 pages 22.69 Kb
Page 18
Image 18
Be sure to check the limit density for

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 18

Obtain liquid tubing size from Tables 1-9, 10, 11, 12 and 15.

Main tubing

LA = ø5/8 (ft.) (Total capacity of indoor unit is 179,400 BTU/h) LB = ø1/2 (ft.) (Total capacity of indoor unit is 131,600 BTU/h) LC = ø3/8 (ft.) (Total capacity of indoor unit is 83,800 BTU/h)

The longest tubing length in this example (LA = 131 ft.)

Distribution joint tubing

 

 

 

Outdoor side

A: ø3/8 (ft.)

B: ø3/8 (ft.)

(from outdoor unit connection tubing)

Indoor side

1: ø3/8 (ft.)

2: ø3/8 (ft.)

3: ø3/8 (ft.)

4: ø3/8 (ft.) (from indoor unit connection tubing)

Obtain charge amount for each tubing size

Note that the charge amounts per 1 meter are different for each liquid tubing size.

ø5/8 (ft.) LA

: 131 ft. 1.99 oz/ft.

=

261 oz

ø1/2 (ft.) LB

: 16 ft. 1.38 oz/ft.

=

22 oz

ø3/8 (ft.) LC + A – B + 1 – 4

: 225 ft. 0.602 oz/ft.

=

135 oz

Total 418 oz

Additional refrigerant charge amount is 418 oz.

CAUTION

Be sure to check the limit density for

the room in which the indoor unit is

installed.

Checking of limit density

Density limit is determined on the basis of the size of a room using an indoor unit of minimum capacity. For instance, when an indoor unit is used in a room (floor area 161 ft.2 ceiling height 8.8 ft. = room volume 1417 ft.3), the graph at right shows that the minimum room volume should be 2455 ft.3 (floor area 279 ft.2) for refrigerant of 418 oz.

<Determination by calculation>

Overall refrigerant charge amount for the air conditioner: oz

(Minimum room volume for indoor unit: ft.3)

= 418 (oz) = 0.29 (oz/ft.3) < 0.3 (oz/ft.3) 1417 (ft.3)

Therefore, openings such as louvers are not required for this

room.

Min. indoor volume

ft.3

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

Range below

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

the density limit of

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

(countermeasures

 

 

 

 

 

not needed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range above

 

 

 

 

 

 

1000

 

 

 

 

 

the density limit of

 

 

 

 

 

500

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

(countermeasures

 

 

 

 

 

0

 

 

 

 

 

needed)

 

 

 

 

 

 

 

 

 

 

 

 

 

0

200

400

600

800

1000

 

 

Total amount of refrigerant

ft.2

454

398

341

area

 

284

floor

227

indoor

170

 

114

Min.

 

 

57

 

 

 

0

 

1200

 

 

oz

 

(when the ceiling is 8.8 ft. high)

18

Page 18
Image 18
Sanyo 85464359982001 Main tubing, Distribution joint tubing, Be sure to check the limit density for