2-3. Shield for Horizontal Exhaust Discharge

It is necessary to install an air-discharge chamber (field supply) to direct exhaust from the fan horizontally if it is diffi- cult to provide a minimum space of 7 ft. between the air-dis- charge outlet and a nearby obstacle. (Fig. 2-8)

In regions with heavy snowfall,

CAUTION the outdoor unit should be provided with a solid, raised plat-

form and snow-proof ducting (field supply). (Fig. 2-9)

2-4. Installing the Outdoor Unit in Heavy Snow Areas

In locations where wind-blown snow can be a problem, snow-proof ducting (field supply) should be fitted to the unit and direct exposure to the wind should be avoided as much as possible. (Fig. 2-10) The following problems may occur if proper countermeasures are not taken:

The fan in the outdoor unit may stop running, causing the unit to be damaged.

There may be no air flow.

The tubing may freeze and burst.

The condenser pressure may drop because of strong wind, and the indoor unit may freeze.

2-5. Precautions When Installing in Heavy Snow

Areas

a)The platform should be higher than the maximum snow depth. (Fig. 2-9)

b)The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air-intake side of the outdoor unit.

c)The platform foundation must be solid and the unit must be secured with anchor bolts.

d)When installing on a roof subject to strong wind, coun- termeasures must be taken to prevent the unit from being overturned.