Table |
|
| Unit: in. (mm) | |||
|
|
|
|
|
| |
BTU/h | 95,500 | 153,600 | 191,100 | 249,100 | 307,100 | |
(kW) | (28.0) | (45.0) | (56.0) | (73.0) | (90.0) | |
|
|
|
|
|
| |
Total system horsepower | 10 | 16 | 20 | 26 | 32 | |
|
|
|
|
|
| |
Combined outdoor units | 10 | 16 | 10 | 16 | 16 | |
10 | 10 | 16 | ||||
|
|
| ||||
|
|
|
|
|
| |
Gas tubing | ø7/8" | |||||
(ø22.22) | (ø28.58) | (ø31.75) | ||||
| ||||||
|
|
|
|
|
| |
Liquid tubing | ø3/8" | ø1/2" | ø5/8" | ø3/4" | ||
(ø9.52) | (ø12.7) | (ø15.88) | (ø19.05) | |||
| ||||||
|
|
|
|
|
|
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension. However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø1/4".
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas and liquid tubes. (Use
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the gas tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
■Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table |
|
|
|
| Unit: in. (mm) | ||||||
|
|
|
| hp = horsepower | |||||||
|
|
|
|
|
|
|
|
|
|
| |
| Below BTU/h | 24,200 | 54,600 | 76,800 | 102,400 | 143,300 | 178,800 | 238,900 | 334,400 | – | |
Total capacity | (2.5 hp) | (6 hp) | (8.1 hp) | (11 hp) | (15 hp) | (19 hp) | (25 hp) | (35 hp) | |||
|
| ||||||||||
after distribution | Over BTU/h | – | 24,200 | 54,600 | 76,800 | 102,400 | 143,300 | 178,800 | 238,900 | 334,400 | |
| |||||||||||
| (2.5 hp) | (6 hp) | (8.1 hp) | (11 hp) | (15 hp) | (19 hp) | (25 hp) | (35 hp) | |||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
| Gas tubing | ø1/2" | ø5/8" | ø3/4" | ø7/8" | ø1" | |||||
| (ø12.7) | (ø15.88) | (ø19.05) | (ø22.22) | (ø25.4) | (ø28.58) | (ø28.58) | (ø31.75) | (ø38.1) | ||
Tubing size |
| ||||||||||
|
|
|
|
|
|
|
|
|
| ||
Liquid tubing | ø3/8" | ø3/8" | ø3/8" | ø3/8" | ø1/2" | ø1/2" | ø5/8" | ø3/4" | ø3/4" | ||
| |||||||||||
| (ø9.52) | (ø9.52) | (ø9.52) | (ø9.52) | (ø12.7) | (ø12.7) | (ø15.88) | (ø19.05) | (ø19.05) | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)
Table | C) |
|
|
| ||||
BTU/h | 95,500 |
|
| 153,600 |
|
|
|
|
(kW) | (28.0) |
|
| (45.0) |
|
|
|
|
| ø7/8" |
|
|
|
|
|
| |
Gas tubing | (ø22.22) |
|
| (ø28.58) |
|
|
|
|
| Brazing connection |
|
|
|
| |||
Liquid tubing | ø3/8" (ø9.52) |
| ø1/2" (ø12.7) |
|
|
|
| |
Flare connection |
|
|
| Balance tube | Gas tube | |||
|
|
|
| |||||
Balance tubing | ø1/4" (ø6.35) |
|
|
| Liquid tube |
| ||
Flare connection |
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
| Unit: in. (mm) |
|
|
|
|
Table |
| Unit: in. (mm) |
| |||||
Indoor unit type | 7 | 9 | 12 | 18 | 24 | 36 | 48 |
|
Gas tubing |
| ø1/2" (ø12.7) |
|
| ø5/8" (ø15.88) |
|
| |
Liquid tubing |
| ø1/4" (ø6.35) |
|
| ø3/8" (ø9.52) |
|
|
Note: Use