Sanyo 85464359982001 installation instructions Size of tubing LO between outdoor units

Models: 85464359982001

1 96
Download 96 pages 22.69 Kb
Page 12
Image 12
■Size of tubing (LO) between outdoor units

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 12

1-6. Tubing Size

 

 

 

 

 

Table 1-9 Main Tubing Size (LA)

 

 

Unit: in. (mm)

 

 

 

 

 

 

BTU/h

95,500

153,600

191,100

249,100

307,100

(kW)

(28.0)

(45.0)

(56.0)

(73.0)

(90.0)

 

 

 

 

 

 

Total system horsepower

10

16

20

26

32

 

 

 

 

 

 

Combined outdoor units

10

16

10

16

16

10

10

16

 

 

 

 

 

 

 

 

 

Gas tubing

ø7/8"

ø1-1/8"

ø1-1/4"

(ø22.22)

(ø28.58)

(ø31.75)

 

 

 

 

 

 

 

Liquid tubing

ø3/8"

ø1/2"

ø5/8"

ø3/4"

(ø9.52)

(ø12.7)

(ø15.88)

(ø19.05)

 

 

 

 

 

 

 

*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension. However extension is not possible if the resulting tubing size is two ranks higher.

*2: The balance tube (outdoor unit tube) diameter is ø1/4".

*3: Type 1 tubing should be used for the refrigerant tubes.

*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas and liquid tubes. (Use field-supply reducers.) (Select from Table 1-9 and Table 1-14.)

*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the gas tubes.

(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)

Size of tubing (LO) between outdoor units

Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.

Table 1-10 Main Tubing Size After Distribution (LB, LC...)

 

 

 

 

Unit: in. (mm)

 

 

 

 

hp = horsepower

 

 

 

 

 

 

 

 

 

 

 

 

Below BTU/h

24,200

54,600

76,800

102,400

143,300

178,800

238,900

334,400

Total capacity

(2.5 hp)

(6 hp)

(8.1 hp)

(11 hp)

(15 hp)

(19 hp)

(25 hp)

(35 hp)

 

 

after distribution

Over BTU/h

24,200

54,600

76,800

102,400

143,300

178,800

238,900

334,400

 

 

(2.5 hp)

(6 hp)

(8.1 hp)

(11 hp)

(15 hp)

(19 hp)

(25 hp)

(35 hp)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas tubing

ø1/2"

ø5/8"

ø3/4"

ø7/8"

ø1"

ø1-1/8"

ø1-1/8"

ø1-1/4"

ø1-1/2"

 

(ø12.7)

(ø15.88)

(ø19.05)

(ø22.22)

(ø25.4)

(ø28.58)

(ø28.58)

(ø31.75)

(ø38.1)

Tubing size

 

 

 

 

 

 

 

 

 

 

 

Liquid tubing

ø3/8"

ø3/8"

ø3/8"

ø3/8"

ø1/2"

ø1/2"

ø5/8"

ø3/4"

ø3/4"

 

 

(ø9.52)

(ø9.52)

(ø9.52)

(ø9.52)

(ø12.7)

(ø12.7)

(ø15.88)

(ø19.05)

(ø19.05)

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)

Table 1-11 Outdoor Unit Tubing Connection Size ( A

C)

 

 

 

BTU/h

95,500

 

 

153,600

 

 

 

 

(kW)

(28.0)

 

 

(45.0)

 

 

 

 

 

ø7/8"

 

 

ø1-1/8"

 

 

 

 

Gas tubing

(ø22.22)

 

 

(ø28.58)

 

 

 

 

 

Brazing connection

 

 

 

 

Liquid tubing

ø3/8" (ø9.52)

 

ø1/2" (ø12.7)

 

 

 

 

Flare connection

 

 

 

Balance tube

Gas tube

 

 

 

 

Balance tubing

ø1/4" (ø6.35)

 

 

 

Liquid tube

 

Flare connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: in. (mm)

 

 

 

 

Table 1-12 Indoor Unit Tubing Connection Size

 

Unit: in. (mm)

 

Indoor unit type

7

9

12

18

24

36

48

 

Gas tubing

 

ø1/2" (ø12.7)

 

 

ø5/8" (ø15.88)

 

 

Liquid tubing

 

ø1/4" (ø6.35)

 

 

ø3/8" (ø9.52)

 

 

Note: Use C1220T-1/2H material for tubing over ø3/4" (ø22.22).

12

Page 12
Image 12
Sanyo 85464359982001 installation instructions Size of tubing LO between outdoor units