4-4. Prepare the Tubing

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 57

4-4. Prepare the Tubing

Material: Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipes and Tubes.” (For tubes that are ø7/8" (ø22.22 mm) or larger, use 1/2H material or H material. For all others use O material.)

Tubing size

Use the tubing size indicated in the table below.

When cutting the tubing, use a tube cutter, and be sure to remove any burrs. (The same applies to distribution tubing (optional).)

When bending the tubes, bend each tube using a radius that is at least 4 times the outer diameter of the tube. When bending, use sufficient care to avoid crushing or damaging the tube

For flaring, use a flare tool, and be sure that flaring is performed correctly.

CAUTION

Use sufficient caution during preparation of the tubing. Seal the tube ends by means of caps or taping to prevent dust, moisture, or other foreign substances from entering the tubes.

Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material O

Material 1/2H • H

 

 

 

 

ø1/4" (ø6.35)

t1/32" (0.8)

ø7/8" (ø22.22)

t5/128" (1.0)

 

 

 

 

ø3/8" (ø9.52)

t1/32" (0.8)

ø1" (ø25.4)

t5/128" (1.0)

 

 

 

 

ø1/2" (ø12.7)

t1/32" (0.8)

ø1-1/8" (ø28.58)

t5/128" (1.0)

 

 

 

 

ø5/8" (ø15.88)

t5/128" (1.0)

ø1-1/4" (ø31.75)

t3/64" (1.1)

 

 

 

 

ø3/4" (ø19.05)

over t5/128" (1.0)

ø1-1/2" (ø38.1)

over t3/64" (1.15)

 

 

ø1-5/8" (ø41.28)

over t3/64" (1.20)

 

 

 

 

4-5. Connect the Tubing

Use the supplied connector tubing. (See figure below.) 09053 type (10 hp)

3

2

1

Refrigerant tubing Connection method Supplied parts used?

1

Gas tubing

Brazing

Yes (ø3/4" ø7/8")

2

Liquid tubing

Flare connection

No

 

 

 

 

3

Balance tube

Flare connection

No

14053 type (16 hp)

3

2

1

Refrigerant tubing Connection method Supplied parts used?

1

Gas tubing

Brazing

Yes (ø1" ø1-1/8")

2

Liquid tubing

Flare connection

No

 

 

 

 

3

Balance tube

Flare connection

No