3.HOW TO INSTALL THE INDOOR UNIT

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 24

3.HOW TO INSTALL THE INDOOR UNIT

4-Way Air Discharge Semi-Concealed Type (X Type) 3-1. Preparation for Suspending

This unit uses a drain pump. Use a carpenter’s level to check that the

Xunit is level.

3-2. Suspending the Indoor Unit

(1)Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely and safely suspended.

(2)Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.

Table 3-1

 

 

Unit: in. (mm)

Length

A

B

C

D

Type

12, 18, 24, 36

31-1/32

28-15/32

34-27/32

34-27/32

(788)

(723)

(885)

(885)

 

 

 

 

 

 

(3)Determine the pitch of the suspension bolts using the supplied full-scale installation diagram. The diagram and table (Fig. 3-3 and Table 3-2) show the relationship between the positions of the suspension fitting, unit, and panel.

Note: For DC Fan Tap Change Procedure for 4-Way Cassette, see page 30.

e-in-anchor

 

 

e-in-plug

Concrete

Insert

Suspension bolt (M10 or 3/8") (field supply)

Fig. 3-1

B (suspension bolt pitch)

Table 3-2

 

 

 

 

Unit: in. (mm)

 

 

 

 

 

 

 

 

Length

A

B

C

D

 

E

 

Type

 

 

12, 18, 24

4-29/64

6-13/16

10-5/64

8-17/64

 

3-15/32

 

(113)

(173)

(256)

(210)

 

(88)

 

 

 

 

36

4-29/64

6-13/16

12-9/16

8-17/64

 

3-15/32

 

(113)

(173)

(319)

(210)

 

(88)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain outlet(other side)

 

Refregerant tubing joint(liquid side)

 

 

(VP25)

 

Suspension lug

D

E

Fig. 3-3

A (suspension bolt pitch)

C (ceiling opening dimension)

Fig. 3-2

Refregerant tubing joint(gas side)

 

C

B

8 (35)

A

3/

 

1-

Power supply outlet

 

Inter-unit control wiring

Unit: in. (mm)

3-3. Placing the Unit Inside the Ceiling

(1)When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 3-4)

Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into position for connection to the unit before placing the unit inside the ceiling.

Over 19/32 (15)

Supplied bolt

– 43/64

17)

15/32

(12 –

Full-scale installation diagram

Unit: in. (mm)

(printed on top of container box)

 

Fig. 3-4

24

Page 24
Image 24