Bus configurations

Bus configuration, examples

Application Other conditions Cableconnector s
20-m localb us Smallplants
Max. 9 participants possible
Max. 20 m bus cable
Standard design redundant
Canonly b e used in instrumentation
rooms.
Theg uidelinesfor ear thing and screen-
ingmus t be observed for the partici-
pants on the local bus.
Ensure inp articular that the partici-
pants have the same ground potential
(equipotentialb onding, 0-V island).
Exceptions are valid for isolated local
bus interface modules N-AS and N-AT.
N1to N2,
N2to N3 etc.: 6DS8201-8 . .
Frontplug on N1: 6DS9 200-8AA
20-m localbus /4-km remote
bus
Large plants
Max. 100 participants possible
Max. 4 km remote bus cable
Max. 32 bus converters UI can be
used, power distribution subrack can
be used for 2 bus converters UI.
Theg uidelinesfor ear thing and screen-
ingmus t be observed for the partici-
pants on the local bus.
Ensure inp articular that the partici-
pants have the same ground potential
(equipotentialb onding, 0-V island).
Exceptions are valid for isolated local
bus interface modules N-AS and N-AT.
N1to UI: 6DS8205- 8 . .
N1to N2,
N2to N3 etc.: 6DS8201-8 . .
20-m localbus /4-km remote
bus, redundant
Large plants
Max. 100 participants possible
Max. 4 km remote bus cable
Max. 32 bus converters UI can be
used, power distribution subrack can
be used for 2 bus converters UI.
Theg uidelinesfor ear thing and screen-
ingmus t be observed for the partici-
pants on the local bus.
Ensure inp articular that the partici-
pants have the same ground potential
(equipotentialb onding, 0-V island).
Exceptions are valid for isolated local
bus interface modules N-AS and N-AT.
N1to U/ 1 and UI2: 6DS8 204-8 . .
N1to N2,
N2to N3 etc.: 6DS8201-8 . .
Individual participant on
4-km remote bus
Medium-sized plants
Individual participant on remote bus
(large distances between individual
participants)
Max. peripheral configuration of
connected ASsystems
Max. 32 participants possible
Max. 4 km remote bus cable
Interface module(s) for 20-m local bus
and bus converter in same cabinet or
subrack.
Power distribution subrack can be
used for 2b us converters UI per
cabinet.
Nto UI: 6DS8 205-8 . .
Individual participant on
4-km remote bus, redundant
Medium-size plants
Individual participant on remote bus
(large distances between individual
participants)
Max. peripheral configuration of
connected ASsystems
Max. 32 participants possible
Max. 4 km remote bus cable
Interface module(s) for 20-m local bus
and bus converter in same cabinet or
subrack.
Power distribution subrack can be
used for 2b us converters UI per
cabinet.
Nto U I1 and UI2: 6DS8 204-8 . .
AF Connector board ”Remote bus” N Interface module for 20-m local bus
FB Remote bus UI Inductive bus converter