Design
Bus configurations
Bus configuration, examples
| 
 | Application | Other conditions | Cable connectors | 
 | 
| Small plants | Can only be used in instrumentation | N1 to N2, | 
 | |
| 
 | Max. 9 participants possible | rooms. | N2 to N3 etc.: | 6DS8  | 
| 
 | 
 | Front plug on N1: | 6DS9  | |
| 
 | Max. 20 m bus cable | The guidelines for earthing and screen- | ||
| 
 | 
 | 
 | ||
| 
 | Standard design redundant | ing must be observed for the partici- | 
 | 
 | 
| 
 | 
 | pants on the local bus. | 
 | 
 | 
| 
 | 
 | Ensure in particular that the partici- | 
 | 
 | 
| 
 | 
 | pants have the same ground potential | 
 | 
 | 
| 
 | 
 | (equipotential bonding,  | 
 | 
 | 
| 
 | 
 | Exceptions are valid for isolated local | 
 | 
 | 
| 
 | 
 | bus interface modules  | 
 | 
 | 
| Large plants | Max. 32 bus converters UI can be | N1 to UI: | 6DS8  | |
| bus | Max. 100 participants possible | used, power distribution subrack can | N1 to N2, | 
 | 
| 
 | be used for 2 bus converters UI. | N2 to N3 etc.: | 6DS8  | |
| 
 | Max. 4 km remote bus cable | |||
| 
 | The guidelines for earthing and screen- | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | ing must be observed for the partici- | 
 | 
 | 
| 
 | 
 | pants on the local bus. | 
 | 
 | 
| 
 | 
 | Ensure in particular that the partici- | 
 | 
 | 
| 
 | 
 | pants have the same ground potential | 
 | 
 | 
| 
 | 
 | (equipotential bonding,  | 
 | 
 | 
| 
 | 
 | Exceptions are valid for isolated local | 
 | 
 | 
| 
 | 
 | bus interface modules  | 
 | 
 | 
| Large plants | Max. 32 bus converters UI can be | N1 to U/1 and UI2: | 6DS8  | |
| bus, redundant | Max. 100 participants possible | used, power distribution subrack can | N1 to N2, | 
 | 
| 
 | be used for 2 bus converters UI. | N2 to N3 etc.: | 6DS8  | |
| 
 | Max. 4 km remote bus cable | |||
| 
 | The guidelines for earthing and screen- | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | ing must be observed for the partici- | 
 | 
 | 
| 
 | 
 | pants on the local bus. | 
 | 
 | 
| 
 | 
 | Ensure in particular that the partici- | 
 | 
 | 
| 
 | 
 | pants have the same ground potential | 
 | 
 | 
| 
 | 
 | (equipotential bonding,  | 
 | 
 | 
| 
 | 
 | Exceptions are valid for isolated local | 
 | 
 | 
| 
 | 
 | bus interface modules  | 
 | 
 | 
| Individual participant on | Interface module(s) for  | N to UI: | 6DS8  | |
| Individual participant on remote bus | and bus converter in same cabinet or | 
 | 
 | |
| 
 | subrack. | 
 | 
 | |
| 
 | (large distances between individual | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | participants) | Power distribution subrack can be | 
 | 
 | 
| 
 | Max. peripheral configuration of | used for 2 bus converters UI per | 
 | 
 | 
| 
 | cabinet. | 
 | 
 | |
| 
 | connected AS systems | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | Max. 32 participants possible | 
 | 
 | 
 | 
| 
 | Max. 4 km remote bus cable | 
 | 
 | 
 | 
| Individual participant on | Interface module(s) for  | N to UI1 and UI2: | 6DS8  | |||||||||||||||||||||
| Individual participant on remote bus | and bus converter in same cabinet or | 
 | 
 | |||||||||||||||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | subrack. | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | (large distances between individual | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | participants) | Power distribution subrack can be | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | Max. peripheral configuration of | used for 2 bus converters UI per | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | cabinet. | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | connected AS systems | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | Max. 32 participants possible | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | Max. 4 km remote bus cable | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| AF | Connector board ”Remote bus” | N | Interface module for  | 
| FB | Remote bus | UI | Inductive bus converter | 
| 3/6 | Siemens PLT 130 . 1994 | 