Overvoltage protection

Configuring notes and ordering data

AF

Connector board ”Remote bus”

GS

Coarse overvoltage protection

Cable lengths: a

< 25 m

ES

Grounding rail

IK

Inhouse cable

b 25 to 50 m

FE

Foundation earth

PA

Equipotential bonding

c

< 50 m

FK

Standard remote bus cable

T

Participant

 

 

FS

Fine overvoltage protection

 

 

 

 

Fig. 4/25 Application of coarse and fine overvoltage protection components with different lengths of cable

Configuring notes

The coarse overvoltage protection must be provided for all re- mote bus cables prior to their exit points from the building and also in the immediate vicinity of the foundation earth connection. The connection between the coarse protection and the founda- tion earth must be kept as short as possible.

The coarse protection is also recommended if the remote bus connects cabinet groups which are positioned more than 50 m from one another within a building. In this case the coarse protection must be installed directly next to the last participant before the longer inhouse cable, and connected to the potential earth of the cabinet.

The fine protection must be provided for each bus participant which is directly connected to a coarse protection component. Fine protection is required for both participants if the distance between the bus participants is > 25 m.

The cable clamps for the various types of remote bus cable are included in the delivery of the overvoltage protection.

Ordering data

 

 

Order No.

Coarse overvoltage protection

 

6DS9 208-8AA

for the CS 275 bus system

 

 

Fine overvoltage protection

 

6DS9 210-8AA

for the CS 275 bus system

 

 

 

 

 

For further information refer to:

 

Order No.

”TELEPERM M, instructions and

 

 

guidelines for planning, installation and operation”

 

 

German

 

C79000-G8000-C417

English

 

C79000-G8076-C417

Siemens PLT 130 . 1994

4/17

Page 34