Overvoltage protection
Configuring notes and ordering data
AF | Connector board ”Remote bus” | GS | Coarse overvoltage protection | Cable lengths: a | < 25 m |
ES | Grounding rail | IK | Inhouse cable | b 25 to 50 m | |
FE | Foundation earth | PA | Equipotential bonding | c | < 50 m |
FK | Standard remote bus cable | T | Participant |
|
|
FS | Fine overvoltage protection |
|
|
|
|
Fig. 4/25 Application of coarse and fine overvoltage protection components with different lengths of cable
Configuring notes
The coarse overvoltage protection must be provided for all re- mote bus cables prior to their exit points from the building and also in the immediate vicinity of the foundation earth connection. The connection between the coarse protection and the founda- tion earth must be kept as short as possible.
The coarse protection is also recommended if the remote bus connects cabinet groups which are positioned more than 50 m from one another within a building. In this case the coarse protection must be installed directly next to the last participant before the longer inhouse cable, and connected to the potential earth of the cabinet.
The fine protection must be provided for each bus participant which is directly connected to a coarse protection component. Fine protection is required for both participants if the distance between the bus participants is > 25 m.
The cable clamps for the various types of remote bus cable are included in the delivery of the overvoltage protection.
Ordering data
|
| Order No. |
Coarse overvoltage protection |
| 6DS9 |
for the CS 275 bus system |
|
|
Fine overvoltage protection |
| 6DS9 |
for the CS 275 bus system |
|
|
|
|
|
For further information refer to: |
| Order No. |
”TELEPERM M, instructions and |
|
|
guidelines for planning, installation and operation” |
|
|
German |
| |
English |
|
Siemens PLT 130 . 1994 | 4/17 |