Siemens PLT130
.
1994

4/18

Remote bus cables
Standard remote bus cable Remote bus cable for special applications
Fig.4/26 Stand ard remoteb us cable
Application
Coaxial cable 2YC(mS) CY1.6/10-75(Z2/5) vs sw is used as
standard as the remote bus cable. The cable may be rout ed in
potentially explosive at mospheres to DIN 57 165/VDE 0165,
Section 5.6.1 and is also suit able for burial in the ground. Max.
permissible length 4000 m.
Coaxial cable 2YC(ms)CY 1.0/6.5--75(Z2/5)vs ws (in-house
cable) can be used indoors. Max. per missible length 2000 m.
Design
From inside to outside:
--Cu conductor, silver-coated --Plastic film
--Polyethylene is olation --Braiding of Cu wires
--Braining of Cu wires -- PVC s heath, black, wall thicknes
--Plastic film --approx. 1.8 mm.
--Winding of metal ribbon
Calculation of the max. permi ssible length of the remote bus
cable when using the standard and in-house cables together:
L
F
= 4000 m --2 L
i
where L
i
Length of in-house cable in m; max. 2000 m
L
F
Length of remotebus cablein m
Technical data
External sheath UV-resistant to VDE 0207, Par t 5,
oil-resistantto IP C EA--S61--402,
flame-retardantto VDE 0472/A
Sheath color
Remotebus cab le
In-house cable
Black
white,p ink longitudinal line
Sheaththick ness
Remotebus cab le
In-house cable
Approx.1.8 mm
Approx.0.65 mm
Outer diameter
Remotebus cab le
In-house cable
(16.8 ¦0.5) mm
(9.5¦0.3) mm
Perm. ambient temperature
Laying
Operation and storage
--5to+50qC
--40to+70qC
Curvature (diameter)
Singleb ending
Repeated bending
300mm; 200 mm ( In-house)
600mm; 400 mm ( In-house)
Tensilestrength
Remote bus
In-house cable
660N
240N
Weight
Remotebus cab le
In-house cable
Approx. 435 kg/km
Approx. 155 kg/km
Ordering data
OrderNo.
Standardremote bus cable
Specify length in plain text
(max. length available in one piece: 1000 m)
V45466-D21-B35
...m
In-housecable
Specify length in plain text
(max. length available in one piece: 250 m; ring)
V45466-D17-B135
...m
Fig.4/27 Remote bus cab lew ithad ditionalar mouring
Application
The cable 2YC(mS)CYbY1.6/10-75(Z2/5) vs (F 0.8 vzk) sw
(Order No. V45466-D21-B65) must be used if the tensile
strength of the standard remote bus cable i s insufficient. This
has additional armouring to i ncrease the tensile strength of the
cable to 25000 N.
If protection against damage by rodents and mechanical dam-
age is required, the cable 2YC(mS)CYbY1.6/10-75 ( Z2/5) vs
(2 B 0,5 vzk) sw (OrderNo. V45466-D21-B55) wi th additional
steel-tape armouring s hould be used. This cable does not have
an increased tensile strength.
Design
Both cables have the same basic desi gn as the standard re-
mote bus cable (see there) but have addit ional armouring.
Max. permissible l ength of remote bus cable: see standard
cable.
Technical data
V45466-D21-B65
Permissibleambient
temperature
Laying
Operation and storage
--5to+50qC
--40to+70qC
Outer diameter 21.3mm
Tensilestrength 25000 N
Weight Approx. 920 kg/km
V45466-D21-B55
Permissibleambient
temperature
Laying
Operation and storage
--5to+50qC
--40to+70qC
Outer diameter 22.1mm
Tensilestrength 660 N
Weight Approx. 923 kg/km
Buriedlay ing of the remoteb us cable
Theremote bus cab lemus t be laid in sand and covered with a suitable mate-
rial,e. g. concrete or p lastics labs. The cable should be laid on a 10-cm thick
layer of sand and then covered with another 10 cm sand. A cable for poten-
tial equilization must be laid above the remote bus cable.
Ordering data
OrderNo
Remotebus cable with additional armouring
¯Toincrease the tensile strength to 25000 N
¯Toprotect against mechanical damage and
damageby rodents
V45466-D21-B65
V45466-D21-B55
Specify length in plain text
(max. length available in one piece: 1000 m) ...m