This catalog is out of date, see note on page 2

Remote bus cables

Standard remote bus cable

Remote bus cable for special applications

 

 

 

 

 

 

Fig. 4/26 Standard remote bus cable

Fig. 4/27 Remote bus cable with additional armouring

Application

Coaxial cable 2YC(mS) CY1.6/10-75(Z2/5) vs sw is used as standard as the remote bus cable. The cable may be routed in potentially explosive atmospheres to DIN 57 165/VDE 0165, Section 5.6.1 and is also suitable for burial in the ground. Max. permissible length 4000 m.

Coaxial cable 2YC(ms)CY 1.0/6.5--75(Z2/5)vs ws (in-house cable) can be used indoors. Max. permissible length 2000 m.

Design

From inside to outside:

- Cu conductor, silver-coated

- Plastic film

- Polyethylene isolation

- Braiding of Cu wires

- Braining of Cu wires

- PVC sheath, black, wall thicknes

- Plastic film

- approx. 1.8 mm.

- Winding of metal ribbon

 

Calculation of the max. permissible length of the remote bus cable when using the standard and in-house cables together:

LF= 4000 m -- 2 Li

where Li Length of in-house cable in m; max. 2000 m LF Length of remote bus cable in m

Technical data

External sheath

UV-resistant to VDE 0207, Part 5,

 

oil-resistant to IPC EA-S61-402,

 

flame-retardant to VDE 0472/A

Sheath color

Black

Remote bus cable

In-house cable

white, pink longitudinal line

Sheath thickness

 

Remote bus cable

Approx. 1.8 mm

In-house cable

Approx. 0.65 mm

Outer diameter

(16.8 ¦ 0.5) mm

Remote bus cable

In-house cable

(9.5 ¦ 0.3) mm

Perm. ambient temperature

- 5 to + 50 qC

Laying

Operation and storage

- 40 to + 70 qC

Curvature (diameter)

 

Single bending

300 mm; 200 mm (In-house)

Repeated bending

600 mm; 400 mm (In-house)

Tensile strength

 

Remote bus

660 N

In-house cable

240 N

Weight

Approx. 435 kg/km

Remote bus cable

In-house cable

Approx. 155 kg/km

 

 

Application

The cable 2YC(mS)CYbY1.6/10-75(Z2/5) vs (F 0.8 vzk) sw (Order No. V45466-D21-B65) must be used if the tensile strength of the standard remote bus cable is insufficient. This has additional armouring to increase the tensile strength of the cable to 25000 N.

If protection against damage by rodents and mechanical dam- age is required, the cable 2YC(mS)CYbY1.6/10-75 (Z2/5) vs (2 B 0,5 vzk) sw (Order No. V45466-D21-B55) with additional steel-tape armouring should be used. This cable does not have an increased tensile strength.

Design

Both cables have the same basic design as the standard re- mote bus cable (see there) but have additional armouring.

Max. permissible length of remote bus cable: see standard cable.

Technical data

 

V45466-D21-B65

 

 

 

Permissible ambient

 

 

temperature

 

 

Laying

- 5 to + 50 qC

 

Operation and storage

- 40 to + 70 qC

 

Outer diameter

21.3 mm

 

Tensile strength

25000 N

 

Weight

Approx. 920 kg/km

 

V45466-D21-B55

 

 

 

Permissible ambient

 

 

temperature

 

 

Laying

- 5 to + 50 qC

 

Operation and storage

- 40 to + 70 qC

 

Outer diameter

22.1 mm

 

Tensile strength

660 N

 

Weight

Approx. 923 kg/km

 

 

 

 

Buried laying of the remote bus cable

The remote bus cable must be laid in sand and covered with a suitable mate- rial, e. g. concrete or plastic slabs. The cable should be laid on a 10-cm thick layer of sand and then covered with another 10 cm sand. A cable for poten- tial equilization must be laid above the remote bus cable.

Ordering data

 

 

Order No.

Standard remote bus cable

 

V45466-D21-B35

Specify length in plain text

 

 

(max. length available in one piece: 1000 m)

 

. . . m

In-house cable

 

V45466-D17-B135

Specify length in plain text

 

 

(max. length available in one piece: 250 m; ring)

 

. . . m

 

 

 

Ordering data

 

 

Order No

Remote bus cable with additional armouring

 

V45466-D21-B65

¯ To increase the tensile strength to 25000 N

 

¯ To protect against mechanical damage and

 

V45466-D21-B55

damage by rodents

 

 

Specify length in plain text

 

 

(max. length available in one piece: 1000 m)

 

. . . m

4/18

Siemens PLT 130 . 1994

Page 35