This catalog is out of date, see note on page 2
Remote bus cables
Standard remote bus cable | Remote bus cable for special applications | |
|
|
|
|
|
|
Fig. 4/26 Standard remote bus cable | Fig. 4/27 Remote bus cable with additional armouring |
Application
Coaxial cable 2YC(mS)
Coaxial cable 2YC(ms)CY
Design
From inside to outside:
- Cu conductor, | - Plastic film |
- Polyethylene isolation | - Braiding of Cu wires |
- Braining of Cu wires | - PVC sheath, black, wall thicknes |
- Plastic film | - approx. 1.8 mm. |
- Winding of metal ribbon |
|
Calculation of the max. permissible length of the remote bus cable when using the standard and
LF= 4000 m
where Li Length of
Technical data
External sheath | |
| |
| |
Sheath color | Black |
Remote bus cable | |
white, pink longitudinal line | |
Sheath thickness |
|
Remote bus cable | Approx. 1.8 mm |
Approx. 0.65 mm | |
Outer diameter | (16.8 ¦ 0.5) mm |
Remote bus cable | |
(9.5 ¦ 0.3) mm | |
Perm. ambient temperature | - 5 to + 50 qC |
Laying | |
Operation and storage | - 40 to + 70 qC |
Curvature (diameter) |
|
Single bending | 300 mm; 200 mm |
Repeated bending | 600 mm; 400 mm |
Tensile strength |
|
Remote bus | 660 N |
240 N | |
Weight | Approx. 435 kg/km |
Remote bus cable | |
Approx. 155 kg/km | |
|
|
Application
The cable
If protection against damage by rodents and mechanical dam- age is required, the cable
Design
Both cables have the same basic design as the standard re- mote bus cable (see there) but have additional armouring.
Max. permissible length of remote bus cable: see standard cable.
Technical data
|
|
| |
| Permissible ambient |
| |
| temperature |
| |
| Laying | - 5 to + 50 qC | |
| Operation and storage | - 40 to + 70 qC | |
| Outer diameter | 21.3 mm | |
| Tensile strength | 25000 N | |
| Weight | Approx. 920 kg/km | |
|
|
| |
| Permissible ambient |
| |
| temperature |
| |
| Laying | - 5 to + 50 qC | |
| Operation and storage | - 40 to + 70 qC | |
| Outer diameter | 22.1 mm | |
| Tensile strength | 660 N | |
| Weight | Approx. 923 kg/km | |
|
|
|
|
Buried laying of the remote bus cable
The remote bus cable must be laid in sand and covered with a suitable mate- rial, e. g. concrete or plastic slabs. The cable should be laid on a
Ordering data
|
| Order No. |
Standard remote bus cable |
| |
Specify length in plain text |
|
|
(max. length available in one piece: 1000 m) |
| . . . m |
| ||
Specify length in plain text |
|
|
(max. length available in one piece: 250 m; ring) |
| . . . m |
|
|
|
Ordering data
|
| Order No |
Remote bus cable with additional armouring |
|
|
¯ To increase the tensile strength to 25000 N |
| |
¯ To protect against mechanical damage and |
|
|
damage by rodents |
|
|
Specify length in plain text |
|
|
(max. length available in one piece: 1000 m) |
| . . . m |
4/18 | Siemens PLT 130 . 1994 |