Siemens PLT130
.
1994

4/12

Remote bus connection subrack S5
Description and ordering data
1 Mains terminals AC 230 V
2 Power supply modules
3 Bus converters UI 6DS4400-8AB
Fig.4/16 Remote bus connection s ubrack S5 6DS4426-8CA
Application
The remote bus connection subrack S5 connects r ack-mounted
systems,especially SIMATICS5-155U programmable control-
lers, to a redundant or non--redundantremote bus . Electrical
isolation between the local and remote bus es is achieved at the
same time.
Non--redundantor redundant DC 24 V or AC 230 V power sup-
plyispossible.
Note: The remote bus connection subrack is not used in the
basiccabinets of the AS 235and AS 235 H automationsystems
andin the OS 265-3 operation andmonitoring system (rack ver-
sion) for DC 24 V.
Design
Single-tier 19-inch subrack with 2 slots for bus conv erter units
UI, optionally with power supply module(s).
The power supply in the case of DV 24 V is f rom the cabinet
supply of the programmable controller, in the cas e of AC 230 V
via the power supply module C79451-A3276 -A1 (redundant as
option).
Technical data
Powersupply
--6DS4 426-8AA
--6DS4 426-8BA and
-- 6DS4 426-8CA
DC24 V ( 20 to 33 V)
permissibleripple $15 %
AC50Hz/60Hz230V+6%/--10%
Power consumption Approx.20 VA
with2 bus conv erter units
Permissibleambient
temperature
--Operation
--Transport and storage
0to+40qC
--40to+70qC
Degreeof protection
toDIN 40 050 IP 00
Protectionclass
(6DS4 426-8BA and
6DS4 426-8CA)
I
Dimensions (hxwxd) 134mmx 485 mm x 260mm
Weight
--Subrack (empty)
--Power supplymodule
--Bus converter unit
Approx.4.5 kg
Approx.1.5 kg
Approx.1.2 kg
E.g. SIMATIC
S5-155U
Remote bus
connectionsub rack S5
Remote bus A
Remote bus B
AF Connector board ”Remote bus” for conver ting the cable cross-section
FS Front plug for 20- m local bus
SV Power supply unit of bus converter
UI Businter face and inductive coupler of bus converter
Fig.4/17 Remote bus connection s ubrack S5 6DS4426-8CA,
functiondiagr am
Ordering data
OrderNo.
Remotebus connection subrack S5
withslots for 2 bus conver ters UI
¯For connectionto DC 24 V,
non-redundant or redundant
6DS4 426--8AA
¯With1 p ower supply module
for AC230 V for non-redundant s upply
to1 or 2 b us converters UI
6DS4 426--8BA
¯With2 p ower supply modules
for AC230 V for redundant sup ply
to2 b us converters UI
6DS4 426--8CA
Thefollowing are required in addition for a
remotebus connection:
Busconverter UI 6DS4 400--8AB
Connectorboard AF ”Remote bus”
withmounting plate
6DS9 203-8DA
Overvoltage fine protection, can be retrofitted 6DS9 210-8AA
Instructions
Remotebus connectionsubrack S5 OrderNo.
German C79000--B8000--C251
English C79000--B8076-- C251
French C79000--B8077--C251
Spanish C79000--B8078--C251
Busconv erter,inductive
German C79000--B8000--C4
English C79000--B8076-- C4
French C79000--B8077--C4
Spanish C79000--B8078--C4
Created with "Chameleon CMYK PDF Creator" for Wolfgang Strozyk at Siemens AG