This catalog is out of date, see note on page 2

Remote bus connection subrack S5

Description and ordering data

1Mains terminals AC 230 V

2 Power supply modules

3 Bus converters UI 6DS4 400-8AB

Fig. 4/16 Remote bus connection subrack S5 6DS4 426-8CA

Application

The remote bus connection subrack S5 connects rack-mounted systems, especially SIMATIC S5-155U programmable control- lers, to a redundant or non--redundant remote bus. Electrical isolation between the local and remote buses is achieved at the same time.

Non--redundant or redundant DC 24 V or AC 230 V power sup- ply is possible.

Note: The remote bus connection subrack is not used in the basic cabinets of the AS 235 and AS 235 H automation systems and in the OS 265-3 operation and monitoring system (rack ver- sion) for DC 24 V.

Design

Single-tier 19-inch subrack with 2 slots for bus converter units UI, optionally with power supply module(s).

The power supply in the case of DV 24 V is from the cabinet supply of the programmable controller, in the case of AC 230 V via the power supply module C79451-A3276-A1 (redundant as option).

Technical data

Power supply

DC 24 V (20 to 33 V)

- 6DS4 426-8AA

- 6DS4 426-8BA and

permissible ripple 15 %

 

- 6DS4 426-8CA

AC 50 Hz/60 Hz 230 V + 6 %/ -10 %

Power consumption

Approx. 20 VA

 

with 2 bus converter units

Permissible ambient

 

temperature

0 to + 40 qC

- Operation

- Transport and storage

- 40 to + 70 qC

Degree of protection

IP 00

to DIN 40 050

Protection class

I

(6DS4 426-8BA and

6DS4 426-8CA)

 

Dimensions (h x w x d)

134 mm x 485 mm x 260 mm

Weight

Approx. 4.5 kg

- Subrack (empty)

- Power supply module

Approx. 1.5 kg

- Bus converter unit

Approx. 1.2 kg

 

 

E. g. SIMATIC

S5-155U

Remote bus connection subrack S5

 

Remote bus A

 

Remote bus B

 

 

AF

Connector board ”Remote bus” for converting the cable cross-section

FS

Front plug for 20-m local bus

SV

Power supply unit of bus converter

UI

Bus interface and inductive coupler of bus converter

Fig. 4/17 Remote bus connection subrack S5 6DS4 426-8CA, function diagram

Ordering data

 

 

Order No.

Remote bus connection subrack S5

 

 

with slots for 2 bus converters UI

 

 

¯ For connection to DC 24 V,

 

6DS4 426-8AA

non-redundant or redundant

 

 

¯ With 1 power supply module

 

6DS4 426-8BA

for AC 230 V for non-redundant supply

 

 

to 1 or 2 bus converters UI

 

 

¯ With 2 power supply modules

 

6DS4 426-8CA

for AC 230 V for redundant supply

 

 

to 2 bus converters UI

 

 

The following are required in addition for a

 

 

remote bus connection:

 

 

Bus converter UI

 

6DS4 400-8AB

 

Connector board AF ”Remote bus”

 

6DS9 203-8DA

 

with mounting plate

 

 

Overvoltage fine protection, can be retrofitted

 

6DS9 210-8AA

 

 

 

Instructions

 

 

Remote bus connection subrack S5

 

Order No.

German

 

C79000-B8000-C251

English

 

C79000-B8076-C251

French

 

C79000-B8077-C251

Spanish

 

C79000-B8078-C251

Bus converter, inductive

 

 

German

 

C79000-B8000-C4

English

 

C79000-B8076-C4

French

 

C79000-B8077-C4

Spanish

 

C79000-B8078-C4

4/12

Siemens PLT 130 . 1994

Page 29
Image 29
Siemens CS 275 manual Remote bus connection subrack S5