4 ELECTRICAL CONNECTIONS

 

 

SITRANS FX300

 

 

 

 

4.3.1 Power supply

INFORMATION!

The supply voltage has to be between 14 VDC and 36 VDC. This is based on the total resistance of the measuring loop. To determine this, add up the resistances of each component in the measuring loop (not including the measuring device).

The required supply voltage can be calculated using the formula below:

Uext. = RL * 22mA + 14V

where

Uext. = the minimum supply voltage and

RL = the total measuring loop resistance is.

INFORMATION!

The power supply has to be able to supply a minimum of 22 mA.

4.3.2 Totalizer / pulse output

The basic units for the totalizer and the pulse output are m3 for volume,

m3norm. for standard volume and kg for mass.

The unit and the conversion factor can be changed in menu item 3.2.8 "Conf.Tot". User specific units (User Def.) can also be entered but the conversion factor must always be entered based on the base unit. For a sample calculation see chapter 6.2.5 "Change units".

The maximum frequency of the pulse output is 0.5 Hz.

Figure 4-3: Pulse output

1fmax 0.5 Hz

2closed

3open

4Pulse 250 ms

34

www.siemens.com/flow

06/2009 - SFIDK.PS.050.F2.02 A5E02100423

Page 34
Image 34
Siemens FX300 manual Power supply, Totalizer / pulse output