OPERATION 6

 

SITRANS FX300

 

 

 

6.5.6 Menu item Setup (firmware version - basic)

Level

Designation

Selection / entry

Explanation

 

 

 

 

 

 

3.1

 

 

 

 

Set display

 

 

 

 

 

 

3.1.1

Error Msg.

 

 

 

Display error

 

 

 

 

 

 

Yes

...

 

Shows error messages in measuring mode in plain text

 

 

 

 

 

 

 

 

alternating with the measured values

 

 

 

 

 

 

 

No

...^

Flashing cursor in the top left corner of the display

 

 

 

 

 

indicates errors.

3.1.2

Cycle.Disp.

 

 

 

Display measured values

 

 

 

 

 

 

Yes

...

 

Cyclically display measured values in measuring mode

 

 

 

 

 

 

 

 

(6 s intervals)

 

 

 

 

 

 

 

No

...^

Do not display measured values cyclically

 

 

 

 

 

 

3.1.3

Code 1

 

 

 

Set security query 1 (menu)

 

 

 

 

 

 

Yes

...

 

Activate access code:

 

 

 

 

 

 

 

 

→→→↑↑↑^^^

 

 

 

 

 

 

 

No

...^

Deactivate access code

 

 

 

 

 

 

 

 

 

 

 

 

3.2

 

 

 

 

I/O settings

 

 

 

 

 

 

3.2.1

4-20mA off

 

 

 

Current output 4-20 mA and error current

 

 

 

 

 

 

4-20mA ...

Current output 4-20 mA

 

 

 

 

 

 

 

 

 

4-20/22E

...

Current output 4-20 mA or error current 22 mA

 

 

 

 

 

 

4-20/3.55E ...^

Current output 4-20 mA or error current 3.55 mA

 

 

 

 

 

 

3.2.5

Function P

 

 

 

Pulse output

 

 

 

 

 

 

Yes

...

 

Activate pulse output

 

 

 

 

 

 

 

 

 

 

No

...^

Deactivate pulse output

 

 

 

 

 

 

3.2.7

Totalizer

 

 

 

Totalizer

 

 

 

 

 

 

Tot. on

...

Start totalizer

 

 

 

 

 

 

 

 

 

Tot. off

...^

Stop totalizer (value is held)

 

 

 

 

 

 

3.2.8

Tot. Conf.

 

 

 

Configure totalizer

 

 

 

 

 

 

 

 

 

 

 

 

(available if Maes.Inst =

m3

 

 

Select totalizer unit for volume flow measurement

 

Volume, see menu item

Unit ...^

 

 

1.1.3)

 

 

 

 

 

0000000000

Enter preset totalizer value

 

 

 

 

m3 ......^

 

 

 

Reset yes /

Reset totalizer /

 

 

Reset no

...^

Do not reset totalizer/

 

 

 

 

 

 

Disp. off /

Display totalizer /

 

 

Disp. on

...^

Do not display totalizer

 

 

 

 

 

 

(available if Maes.Inst =

m3 norm

 

Select totalizer unit for standard volume flow

 

Norm. Vol., see menu

Unit

...^

measurement

 

item 1.1.3)

 

 

 

 

 

0000000000

Enter preset totalizer value

 

 

 

 

m3 norm ......^

 

 

 

Reset yes /

Reset totalizer /

 

 

Reset no

...^

Do not reset totalizer/

 

 

 

 

 

 

Disp. off /

Display totalizer /

 

 

Disp. on

...^

Do not display totalizer

 

 

 

 

 

 

06/2009 - SFIDK.PS.050.F2.02 A5E02100423

www.siemens.com/flow

51