Automation and Drives - SCE
2.7 Types of Controllers
2.7.1 Two Position Controllers
The essential feature of two position controllers consists of their knowing only two modes: “On“ and “Off“
Since theoretically
In the case of the boiler water temperature, the burner would be switched on, for example, when the water temperature drops below the specified setpoint by more than a certain value. The burner continues to run until a certain value that is above the setpoint is exceeded. Only then will the burner be switched off. Another typical example is cooling. Usually, a cooler also does not support a continuous control system, but only knows the states “On“ and “Off“. It is switched on when the actual temperature exceeds the setpoint temperature by a few degrees, and is switched off when the actual temperature is a few degrees too low.
It is therefore typical for the two position controller to periodically fluctuate around the setpoint whose amplitude is roughly that of the hysteresis. The selection of the hysteresis depends on how exactly the setpoint has to be adhered to. If we select a large hysteresis, the actual value can deviate more considerably from the setpoint. If we select a smaller one, the setpoint is adhered to more exactly, but the system would have to switch more frequently. This again has its disadvantages, such as a higher wear of the switching devices, and the actuator or the final control element.
| Preface | Fundamentals | Discontinuous Action Controller Controller Block (S)FB41 | Setting the System Appendix |
|
|
|
|
|
| |
| T I A Training Document | Page 18 of 64 | Module | ||
|
|
|
| B3 | |
Issued: 02/2008 |
|
| Control Engineering with STEP 7 |