Siemens Module B3 manual Output Parameters, Parameter Data Value Range Default Description Type

Models: Module B3

1 64
Download 64 pages 34.52 Kb
Page 64
Image 64

Automation and Drives - SCE

Output Parameters:

Parameter

Data

Value Range

Default

Description

 

Type

 

 

 

LMN

REAL

0.0

 

MANIPULATED VALUE. At the output "Manipulated value",

 

 

 

 

the effectively active manipulated value is read out in the

 

 

 

 

floating point format.

LMN_PER

WORD

W#16#0000

 

MANIPULATED VALUE PERIPHERY. The manipulated value

 

 

 

 

in the periphery format is wired to the controller at the output

 

 

 

 

of "Manipulated value periphery“.

QLMN_HL

BOOL

FALSE

 

HIGH LIMIT OF MANIPULATED VALUE REACHED. The

 

manipulated value is always limited to a high and low limit.

M

 

 

 

 

 

 

The output "High limit of manipulated value reached" signals

 

 

 

 

 

 

 

 

that the high limit has been exceeded.

QLMN_LL

BOOL

FALSE

 

LOW LIMIT OF MANIPULATED VALUE REACHED. The

 

manipulated value is always limited to a high and low limit.

M

 

 

 

 

 

 

The output "Low limit of manipulated value reached" signals

 

 

 

 

 

 

 

 

that the low limit is underrange.

LMN_P

REAL

0.0

 

PROPORTIONALITY COMPONENT. The output "P-

 

 

 

 

component" contains the proportional component of the

 

 

 

 

manipulated variable.

LMN_I

REAL

0.0

 

INTEGRAL COMPONENT. The output "I-component“

 

 

 

 

contains the integral component of the manipulated variable.

 

 

 

 

 

LMN_D

REAL

0.0

 

DERIVATIVE COMPONENT. The output "D-component"

 

 

 

 

contains the derivative component of the manipulated

 

 

 

 

variable.

 

 

 

 

 

PV

REAL

0.0

 

PROCESS VARIABLE / actual value. At the output "Actual

 

 

 

 

value", the effectively active actual value is read out.

ER

REAL

0.0

 

ERROR SIGNAL / System deviation. At the output "System

 

 

 

 

deviation", the effectively active system deviation is read out.

 

 

 

 

 

 

Preface Fundamentals

Discontinuous Action Controller Controller Block (S)FB41

Setting the System Appendix

 

 

 

 

 

 

 

T I A Training Document

Page 64 of 64

Module

 

 

 

B3

Issued: 02/2008

 

Control Engineering with STEP 7

Page 64
Image 64
Siemens Module B3 manual Output Parameters, Parameter Data Value Range Default Description Type