Automation and Drives - SCE

Input Parameters

 

 

 

 

 

 

 

 

Parameter

Data

Value Range

Default

Description

 

Type

 

 

 

COM_RST

BOOL

 

FALSE

COMPLETE RESTART. The block has a

 

complete restart routine that is processed if the

 

 

 

 

 

 

 

 

input is set to "Complete restart".

 

 

 

 

 

MAN_ON

BOOL

 

TRUE

MANUAL VALUE ON / Switch on manual

 

 

 

 

operation. If the input "switch on manual

 

 

 

 

operation" is set, the control loop has been

 

 

 

 

interrupted. A manipulated value is entered as

 

 

 

 

manual value.

PVPER_ON

BOOL

 

FALSE

PROCESS VARIABLE PERIPHERY ON /

 

 

 

 

Actual value

 

 

 

 

Switch on the periphery. If the periphery is to

 

 

 

 

read in the actual value, input PV_PER has to

 

 

 

 

be wired to the periphery, and the input "Switch

 

 

 

 

on actual value periphery" has to be set.

 

 

 

 

 

P_SEL

BOOL

 

TRUE

PROPORTIONAL ACTION ON / Switch on P-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The P-component is switched on if the input

 

 

 

 

"Switch on P-component" is set.

I_SEL

BOOL

 

TRUE

INTEGRAL ACTION ON / Switch on I-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The I-component is switched on if the input

 

 

 

 

"Switch on I- component" is set.

 

 

 

 

 

INT_HOLD

BOOL

 

FALSE

INTEGRAL ACTION HOLD / Freeze I-

 

 

 

 

component. The output of the integrator can be

 

 

 

 

frozen. To this end, the input "Freeze I-

 

 

 

 

component“ is set.

 

 

 

 

 

I_ITL_ON

BOOL

 

FALSE

INITIALIZATION OF THE INTEGRAL ACTION /

 

 

 

 

Set I-component. The output of the integrator

 

 

 

 

can be set to the input I_ITL_VAL. To this end,

 

 

 

 

the input "Set I-component“ has to be set.

 

 

 

 

 

D_SEL

BOOL

 

FALSE

DERIVATIVE ACTION ON / Switch on D-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The D-component is switched on if the input

 

 

 

 

"Switch on D-component" is set.

 

Preface Fundamentals

Discontinuous Action Controller Controller Block (S)FB41

Setting the System Appendix

 

 

 

 

 

 

 

T I A Training Document

Page 61 of 64

Module

 

 

 

B3

Issued: 02/2008

 

Control Engineering with STEP 7

Page 61
Image 61