4. CONTROLLER BLOCK (S)FB41 "CONT_C" AS SOFTWARE PID CONTROLLER IN STEP 7
4.1 Task Definition for PID Standard Controller
In this B3 module, the startup of a PID controller in SIMATIC S7 is demonstrated. The output value of the controlled system is to be kept constant with a continuous controller. Depending on the setting, the controlled system can simulate a P, PT1, or PT2 system. The transfer coefficients Ks and the time constants can also be set. (refer to the description of the controlled system).
Thus, the PLC is the controller, and is connected to the controlled system by means of analog inputs and outputs.
The block (S)FB 41 in the PLC SIMATIC
The following control parameters can be specified:
KP: Proportional component (for (S)FB41 Gain)
TN: Integrator time (for (S)FB41 TI)
TV: Derivative time (for (S)FB41 TD)
|
|
|
|
|
|
|