-Note down the Kp value that has been set as the critical proportional coefficient.

-Specify the duration of a complete oscillation as Tkrit, perhaps with a stop watch by generating the arithmetical mean over several oscillations.

-Multiply the values of Kp,krit and Tkrit with the multipliers according to the table, and thus set the determined values for Kp, Tn and Tv at the controller.