Siemens Module B3 manual Parameter Data Type Value Range Default

Models: Module B3

1 64
Download 64 pages 34.52 Kb
Page 62
Image 62

Parameter

Data Type

Value Range

Default

CYCLE

TIME

>= 1 ms

T#1s

 

 

 

 

SP_INT

REAL

-100.0...+100.0%

0.0

 

 

 

 

PV_IN

REAL

-100.0...+100.0%

0.0

 

 

 

 

PV_PER

WORD

 

W#16#0000

 

 

 

 

MAN

REAL

-100.0...+100.0%

0.0

 

 

 

 

GAIN

REAL

 

2.0

 

 

 

 

TI

TIME

>= CYCLE

T#20s

 

 

 

 

TD

TIME

>= CYCLE

T#10s

 

 

 

 

TM_LAG

TIME

>=CYCLE/2

T#2s

 

 

 

 

DEADB_W

REAL

>=0.0 %

0.0

 

 

 

 

Automation and Drives - SCE

Description

SAMPLE TIME. The time between block calls has to be constant. The input "Sample time" indicates the time between block calls.

INTERNAL SETPOINT. The input "Internal setpoint" is used to specify the setpoint.

PROCESS VARIABLE IN / Actual value input. At the input "Actual value input", a startup value can be parameterized, or an external actual value can be wired in the floating point format.

PROCESS VARIABLE PERIPHERy / Actual value Periphery. The actual value in the periphery format is wired to the controller at the input "Actual value Periphery ".

MANUAL VALUE. The input "Manual value" is used to specify a manual value by means of the operator interface function.

PROPORTIONAL GAIN /Proportional coefficient. The input "Proportional coefficient" indicates controller gain.

RESET TIME / Integration time. The input "Integration time" determines the time response of the integrator.

DERIVATIVE TIME. The input "Derivative time" determines the time response of the differentiator.

TIME LAG OF THE DERIVATE ACTION / Delay of the D-component. The algorithm of the D-component contains a delay that can be parameterized at the input "Time lag of the derivative action".

DEAD BAND WIDTH. The system deviation is taken via a dead band. The "Dead band width" determines the size of the dead band.

 

Preface Fundamentals

Discontinuous Action Controller Controller Block (S)FB41

Setting the System Appendix

 

 

 

 

 

 

 

T I A Training Document

Page 62 of 64

Module

 

 

 

B3

Issued: 02/2008

 

Control Engineering with STEP 7

Page 62
Image 62
Siemens Module B3 manual Parameter Data Type Value Range Default