Check places for indoor unit (Flare nut connection)
Valve cover
Electric parts cover
FILE NO.
To switch the TEST RUN (COOL) mode, press RESET button for 10 sec.
(The beeper will make a short beep.)
Check places for outdoor unit
Fig.
•Check the flare nut connections for the gas leak with a gas leak detector or soap water.
1.Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2.Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3.While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
Hook here
1
1Installation plate
2
Hook
Press
(unhook)
•For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.
Fig.
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
InformationThe product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>•Press and hold the RESET button for about
3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
•To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
Push Push
Fig.
– 58 –