FILE NO.
Outer dia. | Tightening torque | ||
of copper pipe | |||
| |||
|
| ||
∅6.35 mm | 16 to 18 (1.6 to 1.8 kgf·m) | ||
|
|
| |
9.52∅ | mm | 30 to 42 (3.0 to 4.2 kgf·m) | |
|
|
|
Tightening torque of flare pipe connections The operating pressure of R410A is higher than that of R22. (Approx. 1.6 times).
It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at
indoor unit side
Flare at outdoor unit side
Fig.
1.How to shape the pipes
Shape the pipes along the incused line on the outdoor unit.
2.How to fit position of the pipes
Put the edges of the pipes to the place with a distance of 85 mm from the incused line.
| m |
| m |
5 | |
8 |
|
Incused line
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGEEvacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>Be sure to use a vacuum pump with
1.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2.Connect the charge hose to the port of the vacuum pump.
3.Open fully the low pressure side handle of the gauge manifold valve.
4.Operate the vacuum pump to start evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters per minute. Then confirm that the compound pressure gauge reading is − 101 kPa (76 cmHg).
5.Close the low pressure side valve handle of gauge manifold.
6.Open fully the valve stem of the packed valves (both side of Gas and Liquid).
7.Remove the charging hose from the service port.
8.Securely tighten the caps on the packed valves.
Compound pressure gauge | Pressure gauge |
Manifold valve
Handle Lo Handle Hi (Keep full closed)
Charge hose (For R410A only) | Charge hose (For R410A only) |
Connecting pipe |
|
Vacuum pump adapter for
Vacuum
pump
Fig.
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
CAUTION
•KEEP IMPORTANT 4 POINTS FOR PIPINGWORK(1)Take away dust and moisture (Inside of the connecting pipes.)
(2)Tight connection (between pipes and unit)
(3)Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4)Check gas leak (connected points)
– 56 –