<Packed valve handling precautions>

￿Open the valve stem all the way out; but do not try to open it beyond the stopper.

￿Securely tighten the valve stem cap with torque in the following table:

Gas side

30 to 42 N·m

(9.52 mm)

(3.0 to 4.2 kgf·m)

 

 

Liquid side

16 to 18 N·m

(6.35 mm)

(1.6 to 1.8 kgf·m)

 

 

Service port

9 to 10 N·m

(0.9 to 1.0 kgf·m)

 

 

 

 

Hexagonal wrench

 

is required.

FILE NO. SVM-07008

<Stripping length of connection cable>

Terminal block

 

 

 

Power cord

Connecting cable

 

 

 

1 2 3

 

 

L N

10

 

 

10

10

60

10

50

45

40

 

 

Earth line

 

Earth line

Connecting cable

 

Power cord

Fig. 10-3-8

Fig. 10-3-8

10-3-4. Wiring connection

1.Remove the valve cover from the outdoor unit.

2.Connect the connecting cable to the terminal as identified with their respective matched numbers on the terminal block of indoor and outdoor unit.

3.When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.

4.Insulate the unused cords (conductors) from any water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.

Model

RAS-10SKV

 

 

Power source

50 Hz, 220 - 240 V Single phase

 

 

Maximum

8A

running current

 

Installation fuse

25A

rating

 

Power cord

H07RN-F or 245 IEC66 (1.5 mm2

or more)

 

CAUTION

Wrong wiring connection may cause some electrical parts burn out.

Be sure to comply with local codes on running the wire from indoor unit to outdoor unit (size of wire and wiring method etc).

Every wire must be connected firmly.

This installation fuse (25A) must

be used for the power supply line of this air conditioner.

￿If incorrect or incomplete wiring is carried out, it will cause an ignition or smoke.

￿Prepare the power supply for exclusive use with the air conditioner.

￿This product can be connected to the mains. Connection to fixed wiring: A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.

NOTE: Connecting cable

Wire type: More than H07RN-F or 245 IEC66 (1.0 mm2 or more)

– 57 –