FILE NO. SVM-07008

Item

Operation flow and applicable data, etc.

Description

2.Indoor fan <In cooling operation>

motor control

(This operation controls the fan speed at indoor unit side.)

 

 

* Symbols

 

 

 

 

 

 

 

 

 

 

The indoor fan (cross flow fan) is operated by the phase-

 

UH

: Ultra High

 

 

 

 

control induction motor. The fan rotates in 5 stages in

 

H

: High

 

 

 

 

MANUAL mode, and in 5 stages in AUTO mode, respec-

 

M+

: Medium+

 

 

 

 

tively. (Table 1)

 

 

 

 

 

M

: Medium

 

 

 

 

 

 

 

 

 

 

 

 

 

L+

: Low+

 

 

 

 

 

 

 

 

 

 

 

 

 

L

: Low

 

 

 

COOL ON

 

 

 

 

 

 

 

 

 

L-

: Low–

 

 

 

 

 

 

 

 

 

 

 

 

UL

: Ultra Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed setup

 

 

 

 

 

 

 

SUL

: Super Ultra Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MANUAL

 

 

 

 

* The fan speed broadly varies due

 

 

 

 

 

 

 

 

 

 

(Fig. 1)

 

 

 

 

 

 

 

 

 

 

to position of the louver, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The described value indicates one

 

 

AUTO

 

 

 

Indication

 

Fan speed

under condition of inclining

 

 

 

 

 

 

L

 

 

 

W6

downward blowing.

 

 

 

 

 

 

 

 

 

1) When setting the fan speed to L,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L+

 

 

 

(L + M) / 2

 

 

 

 

 

 

 

 

 

 

L+, M, M+ or H on the remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

W9

 

controller, the operation is

 

 

 

 

 

 

 

 

 

 

 

 

performed with the constant

 

 

 

 

 

 

M+

 

 

 

(M + H) / 2

 

 

 

 

 

 

 

 

 

 

 

speed shown in Fig. 1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

WC

2) When setting the fan speed to

 

 

 

 

 

 

 

 

 

 

 

 

AUTO on the remote controller,

 

 

 

 

 

 

 

 

 

 

(Fig. 2)

 

revolution of the fan motor is

 

 

 

 

 

 

 

 

 

 

 

 

controlled to the fan speed level

 

 

 

 

 

 

 

 

 

 

 

 

shown in Fig. 2 and Table 1

 

Ta

 

 

 

Air volume AUTO

 

 

 

 

 

according to the setup tempera-

 

 

 

 

 

 

 

 

 

 

 

ture, room temperature, and heat

[˚C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger temperature.

 

 

 

 

 

 

M+(WB)

 

 

 

 

 

+2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+2.0

a

 

 

*3

*3 : Fan speed = (M + –L) x 3/4 + L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+1.5

b

 

 

*4

*4 : Fan speed = (M + –L) x 2/4 + L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+1.0

c

 

 

*5

*5 : Fan speed = (M + –L) x 1/4 + L

 

 

 

 

+0.5

d

 

 

 

L(W6)

(Linear approximation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from M+ and L)

 

 

 

 

 

Tsc

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Table 1) Indoor fan and air flow rate

Fan speed

 

 

 

RAS-10SKV-E

level

COOL

HEAT

DRY

RAS-10SKV-A

 

 

 

 

Fan speed

Air flow rate

 

 

 

 

(rpm)

(m3/h)

WF

 

UH

 

1350

607

WE

 

H

 

1300

576

WD

UH

M+

UH

1250

554

WC

H

 

H

1200

522

WB

M+

M

M+

1120

486

WA

 

 

M

1100

468

W9

M

L+

 

1040

444

W8

 

L

 

960

402

W7

L+

L-

L+

910

376

W6

L

 

L

880

360

W5

L-

UL

L-

830

334

W4

UL

 

UL

800

318

W3

SUL

 

SUL

700

266

W2

 

SUL

 

650

239

W1

 

 

 

600

213

28