FILE NO. SVM-07008

11-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E

<Check procedure>

1C

1E

Gas leakage,

 

Discharge temp. error,

disconnection of TS/TC

 

gas leakage

sensors (Check code 02, 1C)

 

(Check code 03, 1E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve drive check

 

 

NO

 

 

Is coil of the pulse modulation valve

(P.M.V.) correctly set?

 

 

YES

 

 

 

 

 

 

NO

Is connector of coil connected to inverter?

YES

Is positioning sound of valve (sound hitting to stopper) heard from valve when the air conditioner starts the operation after turning off power of the air conditioner once?

NOTE :

After all the operations stopped by the remote control, the power keeps

being supplied to outdoor unit for approx. 3 minutes. If operating the air NO

conditioner by remote control again just after all the operations stopped by the remote control, positioning of the valve is not performed when outdoor unit

is activated because supplying power to the outdoor unit is not interrupted. After positioning of the valve, activate the compressor and the outdoor fan. It takes approx. 7 seconds for positioning of the valve, and sound ticktack (hitting sound to stopper) is heard for approx. 0.5 seconds at least of that period. As the sound is low, check sound by using screwdriver, etc.

YES

Are temp. sensors of indoor/outdoor units correctly set to the holder?

NOTE :NO The temperature sensors which are used to control electronic control valve

include indoor heat exchanger sensor (TC), outdoor heat exchanger temp. sensor (TE), and outdoor suction temp. sensor (TS).

YES

Set it correctly.

Set it correctly.

Replace coil valve.

Set it correctly.

Gas amount check and valve clogging check

Remove TC sensor connector from the P.C. board in indoor unit.(Remove connector from the P.C. board.)

Operate the air conditioner in COOL mode by TEMP button (Pi sound is heard if keeping pushed for 10 seconds.). The operation enters temporary operation mode which fixes opening degree of P.M.V. and No. of revolution of compressor. Check condensation at outlet of P.M.V., and then check operating pressure from the service port.

Existence of condensation at outlet of P.M.V.

YES

 

 

 

If there is condensation at outlet (1/4 inch=6.35mm valve side),

 

Replace valve.

 

 

 

 

 

the valve is clogged.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the operating pressure from service port, and add gas if pressure is low.

 

 

 

Add gas.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 71 –