FILE NO. SVM-07008

 

 

 

 

 

 

 

 

 

 

 

 

 

Diagnosis/Process flowchart

 

Item

 

Contents

 

Summary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

B

 

 

C

 

 

 

 

 

 

Check

Check winding resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between phases of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor, and resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between outdoor frames by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

NG

 

 

using a tester.

OK if 10M

or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not grounded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

winding of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor.

 

 

 

Is not short-circuited

}

OK if 0.51

0.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between windings.

(Check by a digital tester.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Winding is not opened.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

NG

fan motor

 

 

 

 

 

 

 

com-

 

Operation

Remove connector CN300 of

 

 

 

 

 

 

 

 

 

 

 

 

 

position

 

 

 

 

 

pressor.

 

 

the outdoor fan motor, turn on

 

 

 

 

 

 

 

 

 

 

 

 

 

detect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal.

 

 

 

 

 

 

 

 

 

 

 

 

the power breaker, and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

perform the operation. (Stops

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

though activation is

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prompted.)

 

 

 

 

 

 

 

 

outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check operation within 2

 

 

 

 

 

 

 

 

 

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minutes 20 seconds after

 

 

 

 

 

 

 

 

motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

activation stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Output check of fan motor

a) One or two of three

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

position detect signal>

 

voltages should be 5 V,

 

 

 

 

 

 

 

 

 

 

 

board assembly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

While connecting connector

 

and others should be 0V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5P (CN301) for position

 

(When all are 0V or 5 V,

 

 

 

 

 

Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

detection, using a tester,

 

it is not accepted.)

 

 

 

 

 

 

 

 

 

 

NG

 

 

 

 

 

 

 

 

 

 

 

 

measure voltage between

b) When rotating the fan

 

 

 

compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

winding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-5. Between 5-4 : 5 V

 

slowly with hands, the

 

 

 

resistance.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage between pins

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

should move from 0V to 5 V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Check it with an analog

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

tester.)

 

 

 

control board.

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11-8. How to Check Simply the Main Parts

11-8-1. How to check the P.C. board (Indoor unit)(1)Operating precautions

1)When removing the front panel or the P.C. board, be sure to shut off the power supply breaker.

2)When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.

3)When connecting or disconnecting the connec- tors on the P.C. board, hold the whole housing. Do not pull at the lead wire.

(2)Inspection procedures

1)When a P.C. board is judged to be defective, check for disconnection, burning, or discolora- tion of the copper foil pattern or this P.C. board.

2)The P.C. board consists of the following 2 parts

a.Main P.C. board part:

DC power supply circuit (5 V, 12 V, 15 V), Indoor fan motor control circuit, CPU and peripheral circuits, buzzer, and Driving circuit of louver.

b.Indication unit of infrared ray receiving Infrared ray receiving circuit, LED:

To check defect of the P.C. board, follow the procedure described below.

– 73 –