(3) Checking procedure. |
|
|
|
|
|
|
|
| ||||
|
|
|
|
| Table |
|
|
|
|
| ||
|
|
|
|
|
|
| ||||||
| No. | Procedure | Check Point (Symptom) |
|
| Causes | ||||||
|
|
|
|
|
|
|
|
|
|
|
| |
1 | Shut off the power supply and | 1. Is the fuse blown? |
|
| 1. | Application of shock voltage. | ||||||
|
| remove the P.C. board assembly |
|
|
|
|
|
|
| Overload by | ||
|
| from the electronic parts base. |
|
|
|
|
|
|
| parts. | ||
|
| Remove the connecting cable from |
|
|
|
|
|
|
|
| ||
|
| the terminal block. |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |
2 | Remove the connector for the motor, | Voltage check |
|
|
| 1. | AC power cord is defective. | |||||
|
| and turn the power on. | 1.Between F01 and CN01(pin 1) |
|
| Poor contact of the terminal plate. | ||||||
|
| If the OPERATION lamp blinks | (AC 220 ~ 240 V) |
|
| 2. |
| Capacitor (C121) is defective. | ||||
|
| (0.5 sec. : ON, 0.5 sec. : OFF) when | 2.Between + and −of C03 |
|
| Line filter (L01) is defective. | ||||||
|
| the power turning on, the checking | DC310~DC340V |
|
|
|
| Capacitor (C03) is defective. | ||||
|
| points described as | 3. Between |
| and |
|
|
|
| Diode (D01,D02,D03, or D04) | ||
|
| 5V | GND |
|
| |||||||
|
| column are not necessary to | 4. Between |
| and |
|
|
|
| is defective. | ||
|
| 12V | GND |
|
| |||||||
|
| perform. |
|
|
|
|
| 3. |
| T101 is defective. | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
3 | Start the operation with the system | 1. All indicators light for 3 sec.. |
| } | Defective indicator, or poor | |||||||
|
| which the time of the restart delay | 2. Indicators do not indicate normally |
| ||||||||
|
|
| housing assembly. (CN21) | |||||||||
|
| timer is shortened. | after approximate 3 sec.. |
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||
4 | Make the operation status by | 1. Compressor does not operate. | 1.The temperature of the indoor | |||||||||
|
| pressing once the [ |
| ] button. | 2. OPERATION lamp blinks. |
| heat exchanger is abnormally | |||||
|
|
|
| |||||||||
|
|
|
| |||||||||
|
| 1.The time of the restart delay timer |
|
|
|
|
|
| lower. | |||
|
| is shortened. |
|
|
|
|
| 2.Poor contact of the heat | ||||
|
| 2.Cool operation |
|
|
|
|
|
| exchanger sensor. (The connector | |||
|
| 3.Air volume [AUTO] |
|
|
|
|
|
| is disconnected.) (CN62) | |||
|
| 4. Make the setting temperature lower |
|
|
|
|
| 3.Heat exchanger sensor, main | ||||
|
| enough than room temperature. |
|
|
|
|
|
| P.C. board are defective. (Refer to | |||
|
| 5. Continuous operation. |
|
|
|
|
| 4.Main P.C. board is defective. | ||||
|
|
|
|
|
|
|
|
|
|
| ||
5 | The status of No. 4 is continued, and | 1. Compressor does not operate. | 1. The temperature of the heat | |||||||||
|
| make the following condition. | 2. OPERATION lamp blinks. |
| exchanger is abnormally high. | |||||||
|
| 1.Heat operation |
|
|
|
|
| 2. The heat exchanger sensor | ||||
|
| 2.Make the setting temperature |
|
|
|
|
|
| connector has | |||
|
| higher enough than room |
|
|
|
|
| 3. The heat exchanger sensor is | ||||
|
| temperature. |
|
|
|
|
|
| defective. | |||
|
|
|
|
|
|
|
|
|
| 4. P.C. board is defective. | ||
|
|
|
|
|
|
|
|
|
|
| ||
6 | Turn the power on after connecting | 1.Motor does not rotate. (The key | 1. Poor contact of the motor | |||||||||
|
| the motor connector. Start the | operation is accepted.) |
| connector. | |||||||
|
| operation with the following | 2. The Motor rotates, but it vibrates | 2. Fan motor is defective | ||||||||
|
| condition. | too much. |
|
|
|
|
|
|
|
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation