Concealed Duct High Static Pressure | Installation Manual |
nError codes and parts to be checked
| Wired remote |
|
|
| Air | |
| controller | Main defective parts | Judging | Parts to be checked / error description | ||
| display | conditioner | ||||
| device | |||||
|
|
|
| status | ||
| Indication |
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| No header remote controller | Remote | Incorrect remote controller setting – The header remote controller |
| |
| E01 | has not been set (including two remote controllers). | ∗ | |||
|
| |||||
|
| controller |
| |||
|
| Remote controller communication error | No signal can be received from the indoor unit. |
| ||
|
|
|
| |||
|
|
|
|
|
| |
| E02 | Remote controller transmission error | Remote | System interconnecting wires, indoor P.C. board, remote controller – | ∗ | |
|
|
| controller | No signal can be sent to the indoor unit. |
| |
| E03 | Indoor | Indoor | Remote controller, network adapter, indoor P.C. board – No data is | ||
| communication error | received from the remote controller or network adapter. | ||||
|
|
|
| |||
|
|
|
|
|
| |
|
| Indoor |
| System interconnecting wires, indoor P.C. board, outdoor P.C. board. |
| |
| E04 | communication error | Indoor | |||
|
| – Serial communication error between indoor unit and outdoor unit | ||||
|
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
| E08 | Duplicated indoor addresses « | Indoor | Indoor address setting error – | ||
| The same address as the | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
| Remote controller address setting error – Two remote controllers are |
| |
| E09 | Duplicated header remote controllers | Remote | set as header in the | ∗ | |
|
| |||||
|
|
| controller | (∗ The header indoor unit stops raising alarm and follower indoor |
| |
|
|
|
| units continue to operate.) |
| |
|
|
|
|
|
| |
| E10 | Indoor | Indoor P.C. board – Communication error between main MCU and | |||
| motor microcomputer MCU | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| Header indoor |
| Indoor P.C. board – |
| |
– | E18 | Indoor | Regular communication is not possible between header and follower | |||
regular communication error | ||||||
|
| indoor units or between twin header (main) and follower (sub) units. |
| |||
|
|
|
| |||
101 |
|
|
|
|
| |
E31 | IPDU communication error | Outdoor | Communication error between IPDU and CDB | Entire stop | ||
|
|
|
|
| ||
F01 | Indoor unit heat exchanger sensor | Indoor | Heat exchanger sensor (TCJ), indoor P.C. board – | |||
– | (TCJ) error | |||||
|
|
| ||||
|
|
|
|
| ||
| F02 | Indoor unit heat exchanger sensor (TC) | Indoor | Heat exchanger sensor (TC), indoor P.C. board – | ||
| error | |||||
|
|
|
| |||
|
|
|
|
|
| |
| F04 | Outdoor unit discharge temp. sensor | Outdoor | Outdoor temp. sensor (TD), outdoor P.C. board – | Entire stop | |
| (TD) error | |||||
|
|
|
| |||
|
|
|
|
|
| |
| F06 | Outdoor unit temp. sensor (TE/TS) | Outdoor | Outdoor temp. sensors (TE/TS), outdoor P.C. board – | Entire stop | |
| error | |||||
|
|
|
| |||
|
|
|
|
|
| |
| F07 | TL sensor error | Outdoor | TL sensor may be displaced, disconnected or | Entire stop | |
|
|
|
|
|
| |
| F08 | Outdoor unit outside air temp. sensor | Outdoor | Outdoor temp. sensor (TO), outdoor P.C. board – | Operation | |
| error | continued | ||||
|
|
| ||||
|
|
|
|
|
| |
| F10 | Indoor unit room temp. sensor (TA) | Indoor | Room temp. sensor (TA), indoor P.C. board – | ||
| error | circuit of the room temp. sensor (TA) was detected. | ||||
|
|
|
| |||
|
|
|
|
|
| |
| F12 | TS (1) sensor error | Outdoor | TS (1) sensor may be displaced, disconnected or | Entire stop | |
|
|
|
|
|
| |
| F13 | Heat sink sensor error | Outdoor | Abnormal temperature was detected by the temp. sensor of the IGBT | Entire stop | |
| heat sink. | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
| F15 | Temp. sensor connection error | Outdoor | Temp. sensor (TE/TS) may be connected incorrectly. | Entire stop | |
|
|
|
|
|
| |
| F29 | Indoor unit, other P.C. board error | Indoor | Indoor P.C. board – EEPROM error | ||
|
|
|
|
|
| |
| F31 | Outdoor unit P.C. board | Outdoor | Outdoor P.C. board – In the case of EEPROM error. | Entire stop | |
|
|
|
|
|
| |
|
|
|
| Current detect circuit, power voltage – |
| |
| H01 | Outdoor unit compressor breakdown | Outdoor | Minimum frequency was reached in the current releasing control or | Entire stop | |
|
|
|
|
| ||
|
|
|
|
|
| |
| H02 | Outdoor unit compressor lock | Outdoor | Compressor circuit – Compressor lock was detected. | Entire stop | |
|
|
|
|
|
| |
| H03 | Outdoor unit current detect circuit error | Outdoor | Current detect circuit, outdoor unit P.C. board – Abnormal current | Entire stop | |
| was detected in | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
| H04 | Case thermostat operation (1) | Outdoor | Malfunction of the case thermostat. | Entire stop | |
|
|
|
|
|
| |
|
|
|
| Current, |
| |
| H06 | Outdoor unit | Outdoor | Ps pressure sensor error was detected or | Entire stop | |
|
|
|
| operation was activated. |
| |
|
|
|
|
|
|
Concealed Duct High Static Pressure | Installation Manual |
Wired remote |
|
|
| Air | |
controller | Main defective parts | Judging | Parts to be checked / error description | ||
display | conditioner | ||||
device | |||||
|
|
| status | ||
Indication |
|
|
| ||
|
|
|
| ||
|
|
|
|
| |
L03 | Duplicated header indoor units « | Indoor | Indoor address setting error – | Entire stop | |
| There are two or more header units in the group. | ||||
|
|
|
| ||
|
|
|
|
| |
L07 | Group line in individual indoor unit | Indoor | Indoor address setting error – There is at least one | Entire stop | |
« | indoor unit among individual indoor units. | ||||
|
|
| |||
|
|
|
|
| |
L08 | Indoor group address not set « | Indoor | Indoor address setting error – Indoor address group has not been set. | Entire stop | |
|
|
|
|
| |
L09 | Indoor power level not set | Indoor | Indoor power level has not been set. | Entire stop | |
|
|
|
|
| |
L10 | Outdoor unit P.C. board | Outdoor | In the case of outdoor P.C. board jumper wire (for service) setting error. | Entire stop | |
|
|
|
|
| |
|
| Network | Address setting, central control remote controller, network adapter |
| |
L20 | LAN communication error | adapter | – Duplication of address in central control communication. | ||
|
| central control |
|
| |
|
|
|
|
| |
|
|
| Other outdoor unit error Entire stop |
| |
L29 | Other outdoor unit error | Outdoor | 1) Communication error between IPDU MCU and CDB MCU | Entire stop | |
2) Abnormal temperature was detected by the heat sink temp. | |||||
|
|
|
| ||
|
|
| sensor in IGBT. |
| |
|
|
|
|
| |
L30 | Abnormal external input into | Indoor | External devices, outdoor unit P.C. board – Abnormal stop due to | Entire stop | |
indoor unit (interlock) |
| incorrect external input into CN80 |
| ||
|
|
| |||
|
|
|
|
| |
|
|
| Power supply phase sequence, outdoor unit P.C. board | Operation | |
L31 | Phase sequence error, etc. | Outdoor | continued | ||
– Abnormal phase sequence of the | (thermostat | ||||
|
|
| |||
|
|
|
| OFF) | |
|
|
|
|
| |
P01 | Indoor unit fan error | Indoor | Indoor fan motor, indoor P.C. board – Indoor AC fan error | Entire stop | |
(fan motor thermal relay activated) was detected. | |||||
|
|
|
| ||
|
|
|
|
| |
P03 | Outdoor unit discharge temp. error | Outdoor | An error was detected in the discharge temp. releasing control. | Entire stop | |
|
|
|
|
| |
P04 | Outdoor unit | Outdoor | Entire stop | ||
error | detected in the | ||||
|
|
| |||
|
|
|
|
| |
P05 | Open phase detected | Outdoor | The power supply wire may be connected incorrectly. | Entire stop | |
Check open phase and voltages of the power supply. | |||||
|
|
|
| ||
|
|
|
|
| |
P07 | Heat sink overheat | Outdoor | Abnormal temperature was detected by the temp. sensor of the IGBT | Entire stop | |
heat sink. | |||||
|
|
|
| ||
|
|
|
|
| |
P10 | Indoor unit water overflow | Indoor | Drain pipe, clogging of drainage, float switch circuit, indoor P.C. board | Entire stop | |
detected | – Drainage is out of order or the float switch was activated. | ||||
|
|
| |||
|
|
|
|
| |
P15 | Gas leakage detected | Outdoor | There may be gas leakage from the pipe or connecting part. | Entire stop | |
Check for gas leakage. | |||||
|
|
|
| ||
|
|
|
|
| |
|
| Outdoor | |||
P19 | – An error was detected due to temperature drop of the indoor unit | ||||
(Indoor) | |||||
|
| heat exchanger sensor when heating. | |||
|
|
|
| ||
|
|
|
|
| |
P20 | Outdoor | Entire stop | |||
|
|
|
|
| |
P22 | Outdoor unit fan error | Outdoor | Outdoor unit fan motor, outdoor unit P.C. board – An error (overcurrent, | Entire stop | |
locking, etc.) was detected in the outdoor unit fan drive circuit. | |||||
|
|
|
| ||
|
|
|
|
| |
|
|
| IGBT, outdoor unit P.C. board, inverter wiring, compressor |
| |
P26 | Outdoor unit inverter Idc activated | Outdoor | – | Entire stop | |
|
|
|
| ||
|
|
|
|
| |
P29 | Outdoor unit position error | Outdoor | Outdoor unit P.C. board, | Entire stop | |
– Compressor motor position error was detected. | |||||
|
|
|
| ||
|
|
|
|
| |
P31 | Other indoor unit error | Indoor | Another indoor unit in the group is raising an alarm. | Entire stop | |
|
| ||||
E03/L07/L03/L08 alarm check locations and error description | |||||
|
|
| |||
|
|
|
|
|
«: The air conditioner automatically enters the
– 39 – | – 40 – |