Procedure 6

When settings have been completed, push nRemote controller switch monitoring function button to determine the settings.

When nFilter sign setting button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote controller is accepted.)

Installation Manual

nPower saving mode

1.Push ( 1 → 2 → 3 → 4 → 5 → 6 ).SET DATA button for at least four seconds when the air conditioner is not working.

Filter sign term flashes.

Indicates CODE No. “C2.”

2. Select an indoor unit to be set by pushing (left side of the button).

Each time you push the button, unit numbers change as follows:

Concealed Duct High Static Pressure

Installation Manual

nRemote controller switch monitoring function

This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.

nFilter sign setting

According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

( 1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [01].

For the [SET DATA] in Procedure 4, select the SET DATA of filter sign term from the following table.

 

SET DATA

Filter sign term

 

 

 

 

0000
None

 

 

 

0001
150H

96

0002
2500H (Factory default)

 

 

0003
5000H

 

 

0004
10000H

 

UNIT No.

 

UNIT No.

 

UNIT No.

1-1

 

1-2

 

1-3

UNIT No.

1-4

The fan of the selected unit runs.

3.Adjust the power save setting by pushing

TIME 0000 / None buttons.

Each push of the button changes the power level by 1% within the range from 100% to 50%.

The factory default is 75%.

2

4

1 3

1.Push 0001 and 150H buttons simultaneously for at least 4 seconds to call the service monitor mode. The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No. ￿￿ is also displayed.

2.Pushing TEMP. 0002 / 2500H (Factory default) buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)

3.Pushing 00035000H000410000H (left side of the button), select an indoor unit to be monitored.

The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.

4.Push 2 button to return to the normal display.

n To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised.

Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

( 1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [06].

For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.

SET DATA

Detection temperature shift value

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C (Factory default)

0003

+3°C

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

Setting of power level in power saving mode

4.Determine the setting by pushing n To secure better effect of heating button.

5.Push Detection temperature shift value button to complete the setting.

 

Indoor unit data

 

 

CODE No.

Data name

 

 

01

Room temperature (remote controller)

 

 

02

Indoor unit intake air temperature (TA)

 

 

03

Indoor unit heat exchanger (coil)

temperature (TCJ)

 

 

 

04

Indoor unit heat exchanger (coil)

temperature (TC)

 

 

 

F3

Indoor unit fan cumulative operating hours

(× 1 h)

 

 

 

 

Outdoor unit data

 

 

CODE No.

Data name

 

 

60

Outdoor unit heat exchanger (coil)
temperature (TE)

 

 

 

61

Outside air temperature (TO)

 

 

62

Compressor discharge temperature (TD)

 

 

63

Compressor suction temperature (TS)

 

 

64

 

 

65

Heatsink temperature (THS)

 

 

6A

Operating current (× 1/10)

 

 

F1

Compressor cumulative operating hours

(× 100)

 

 

 

– 29 –