Concealed Duct High Static Pressure
Procedure 6
When settings have been completed, push button to determine the settings.
When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote controller is accepted.)
Installation Manual
nPower saving mode
1.Push button for at least four seconds when the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2. Select an indoor unit to be set by pushing (left side of the button).
Each time you push the button, unit numbers change as follows:
Concealed Duct High Static Pressure | Installation Manual |
nRemote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.
nFilter sign setting
According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
( 1 → 2 → 3 → 4 → 5 → 6 ).
•For the CODE No. in Procedure 3, specify [01].
•For the [SET DATA] in Procedure 4, select the SET DATA of filter sign term from the following table.
| SET DATA | Filter sign term | |
|
|
| |
| 0000 | None | |
|
|
| |
– | 0001 | 150H | |
96 | 0002 | 2500H (Factory default) | |
|
| ||
0003 | 5000H | ||
– | |||
|
| ||
0004 | 10000H | ||
|
UNIT No. |
| UNIT No. |
| UNIT No. |
|
|
UNIT No.
The fan of the selected unit runs.
3.Adjust the power save setting by pushing
TIME /
buttons.
Each push of the button changes the power level by 1% within the range from 100% to 50%.
∗ The factory default is 75%.
2
4
1 3
1.Push and
buttons simultaneously for at least 4 seconds to call the service monitor mode. The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No. is also displayed.
2.Pushing TEMP. /
buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)
3.Pushing (left side of the button), select an indoor unit to be monitored.
The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.
4.Push button to return to the normal display.
n To secure better effect of heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised.
Also use a circulator, etc. to circulate heat air near the ceiling.
Follow to the basic operation procedure
( 1 → 2 → 3 → 4 → 5 → 6 ).
•For the CODE No. in Procedure 3, specify [06].
•For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.
SET DATA | Detection temperature shift value |
|
|
0000 | No shift |
|
|
0001 | +1°C |
|
|
0002 | +2°C (Factory default) |
0003 | +3°C |
0004 | +4°C |
|
|
0005 | +5°C |
|
|
0006 | +6°C |
|
|
Setting of power level in power saving mode
4.Determine the setting by pushing button.
5.Push button to complete the setting.
| Indoor unit data | |
|
| |
CODE No. | Data name | |
|
| |
01 | Room temperature (remote controller) | |
|
| |
02 | Indoor unit intake air temperature (TA) | |
|
| |
03 | Indoor unit heat exchanger (coil) | |
temperature (TCJ) | ||
| ||
|
| |
04 | Indoor unit heat exchanger (coil) | |
temperature (TC) | ||
| ||
|
| |
F3 | Indoor unit fan cumulative operating hours | |
(× 1 h) | ||
| ||
|
|
| Outdoor unit data | |
|
| |
CODE No. | Data name | |
|
| |
60 | Outdoor unit heat exchanger (coil) | |
temperature (TE) | ||
| ||
|
| |
61 | Outside air temperature (TO) | |
|
| |
62 | Compressor discharge temperature (TD) | |
|
| |
63 | Compressor suction temperature (TS) | |
|
| |
64 | — | |
|
| |
65 | Heatsink temperature (THS) | |
|
| |
6A | Operating current (× 1/10) | |
|
| |
F1 | Compressor cumulative operating hours | |
(× 100) | ||
| ||
|
|