Toshiba RAV-SM2242DT-TR 88, n Diagrams for making connecting flanges, nDuct design, Unit: mm

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 88
Image 88
n Diagrams for making connecting flanges

Concealed Duct High Static Pressure

Installation Manual

n Diagrams for making connecting flanges

(Unit: mm)

The connecting flange (Incl. the fixing screw) is not supplied to the indoor unit.

When the connecting flange is necessary, produce them in locally.

Drawing figure is as follows. (Material: Galvanized steel plate, thickness of 1.6 mm)

<Air outlet port flange>

 

 

 

1130

 

 

65

250

250

250

250

65

12

 

 

 

 

 

 

 

25

1080

 

 

 

 

 

 

 

394

370

25

 

344

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

25

 

10-Ø8 hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Air inlet port connecting flange>

Concealed Duct High Static Pressure

Installation Manual

nDuct design

1.In order to prevent short circuits, design the duct installation, so that the intake and discharge openings are not adjacent to each other.

2.The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and install the air filter (Locally procured).

If no air filter is installed, the heat exchanger will be blocked by dust, which may cause the malfunction of air conditioner or the water leakage.

<Duct installation example (First floor)>

Air outlet chamber

 

High efficiency filter

(with heat insulation)

inserting port

 

Air outlet port

 

Pre filter

Flexible duct hanging band

connecting flange

 

inserting port

 

 

 

Air inlet port

Duct hose (with heat insulation)

Indoor unit

connecting flange

Electrical

Filter

Air inlet

control box

chamber

chamber

– 88 –

430

40612<Air outlet port flange>

25

 

 

 

1130

 

 

65

250

250

250

250

65

 

 

25

1080

 

 

 

 

 

 

 

380

25

 

 

Ceiling

Air outlet port

Air outlet port

Duct hose

 

 

 

Check port or carrying

 

Check port cap in port (600 × 600)

To ground floor

 

From ground floor

12

 

25

10-Ø8 hole

 

 

 

NOTE

All duct connection between units except outdoor unit must be procured and enforced locally.

– 13 –

– 14 –

Page 88
Image 88
Toshiba RAV-SM2242DT-TR 88, n Diagrams for making connecting flanges, nDuct design, Concealed Duct High Static Pressure