Toshiba RAV-SM2802DT-E 27, Item, Outline of specifications, Remarks, Setup at shipment

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 27
Image 27
Setup at shipment

No.

Item

Outline of specifications

Remarks

 

 

 

 

8

High-temp. release

1) The heating operation is performed as follows based

 

 

control

on the detected temperature of Tc sensor or Tcj sensor.

 

 

 

• When [M] zone is detected, the commanded frequency

 

 

 

is decreased from the real operation frequency.

 

 

 

After then the commanded frequency changes every

 

 

 

30 seconds while operation is performed in [M] zone.

 

 

 

• In [N] zone, the commanded frequency is held.

 

 

 

• When [L] zone is detected, the commanded fre-

 

 

 

quency is returned to the original value by approx.

 

 

 

6Hz every 60 seconds.

 

Setup at shipment

Tc (˚C)

 

 

M

 

 

Tcj A

 

 

Control temp. (°C)

 

 

N

 

 

 

 

 

 

 

 

A

B

B

 

 

 

 

 

 

 

 

 

 

 

 

 

56 (54)

52 (52)

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

When the operation has started or when Tc or Tcj < 30°C

Same status as that

 

 

at start of the operation or after operation start,

when “thermostat-OFF”

 

 

temperature is controlled between values in parentheses

 

 

 

of A and B.

 

 

 

 

 

 

9

Drain pump control

1)

In cooling operation, the drain pump is usually

 

 

(When drain up kit

 

operated.

 

 

sold separately is

2)

If the float switch works while drain pump drives, the

Check code [P10]

 

mounted)

 

compressor stops, the drain pump continues the

 

 

 

 

operation, and a check code is output.

 

 

 

3)

If the float switch works while drain pump stops, the

 

 

 

 

compressor stops and the drain pump operates. If the

 

 

 

 

float switch keeps operating for approx. 4 minutes, a

 

 

 

 

check code is output.

 

 

 

 

 

 

10

After-heat

When heating operation stops, in some cases, the indoor

 

 

elimination

fan operates with [FAN] for approx. 30 seconds.

 

 

 

 

 

 

11

HA control

1)

ON/OFF is possible by HA signal input from the

Use for remote start/stop

 

 

 

remote site when it is connected to the wireless

When using HA terminal

 

 

 

remote unit or the remote Start/Stop I/F.

 

 

 

(CN61), the connecting

 

 

2)

ON/OFF status is output to HA output terminal.

connector sold sepa-

 

 

3)

HA I/O specification conforms to JEMA Standard.

rately is necessary.

 

 

 

 

In a group operation,

 

 

 

 

connect it to any of

 

 

 

 

master or follower indoor

 

 

 

 

unit for use.

– 27 –