Toshiba RAV-SM2802DT-E 54, Table, Type: CODE No, Indoor unit capacity: CODE No, Item

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 54
Image 54

Table 1

DN

Item

Setting data

Factory-set value

 

 

 

 

01

Filter sign lighting time

 

Depending on Type

 

 

 

 

02

Filter pollution leve

 

0000: standard

 

 

 

 

03

Central control address

 

0099: Not determined

 

 

 

 

06

Heating suction temperature shift

 

0002: +2°C

 

(flooring installation type: 0)

 

 

 

 

 

 

 

OF

Cooling only

 

0000: Heat pump

 

 

 

 

10

Type

 

Depending on model type

 

 

 

 

11

Indoor unit capacity

 

Depending on capacity type

 

 

 

 

12

System address

 

0099: Not determined

 

 

 

 

13

Indoor unit address

 

0099: Not determined

 

 

 

 

14

Group address

 

0099: Not determined

 

 

 

 

1E

Temperature range of cooling/heating

 

0003: 3 deg (Ts ± 1.5)

automatic SW control point

 

 

 

 

 

 

 

 

28

Power failure automatic recovery

 

0000: None

 

 

 

 

2b

Thermo output SW (T10 ƒ )

 

0000: Thermo ON

 

 

 

 

31

Ventilation fan (standalone)

 

0000: Not available

 

 

 

 

32

Sensor SW (Selection of static pressure)

 

0000: Body sensor

 

 

 

 

40

Humidifier control (+ drain pump control)

 

0003: Humidifier ON + Pump OFF

 

 

 

 

60

Timer setting (wired remote controller)

 

0000: Available

 

 

 

 

Table 2. Type: CODE No. 10

Setting data

Type

Type name abb.

 

 

 

0006

Concealed Duct High Static Type

RAV-SM∗∗∗DT-E (TR)

 

 

 

Table 3. Indoor unit capacity: CODE No. 11

Setting data

Type

 

 

0000

Disable

 

 

0021

224

 

 

0023

280

 

 

EEPROM initial value on the P.C. board for indoor unit servicing.

– 54 –

Page 54
Image 54
Toshiba RAV-SM2802DT-E 54, Table, Type: CODE No, Indoor unit capacity: CODE No, Item, Setting data, Factory-setvalue