The refrigerant used by this air conditioner is the R410A.

 

Check the used refrigerant name and use tools and materials of the parts which match with it.

 

For the products which use R410A refrigerant, the refrigerant name is indicated at a position on

 

the outdoor unit where is easy to see.

 

To prevent miss-charging, the route of the service port is changed from one of the former R22.

 

For an air conditioner which uses R410A, never use other refrigerant than R410A.

 

For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.

 

If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating

 

cycle and an injury due to breakage may be caused.

 

Do not charge refrigerant additionally.

 

If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the

 

refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over

 

the specified standard amount is charged and an abnormal high pressure is applied to the inside

 

of the refrigerating cycle resulted in cause of breakage or injury.

Refrigerant

Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute

 

vacuuming, and then newly recharge the specified amount of liquid refrigerant.

 

In this time, never charge the refrigerant over the specified amount.

 

When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other

 

than R410A into the specified refrigerant.

 

If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating

 

cycle resulted in cause of injury due to breakage.

 

After installation work, check the refrigerant gas does not leak.

 

If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such

 

as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.

 

Never recover the refrigerant into the outdoor unit.

 

When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.

 

The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as

 

breakage or injury is caused.

 

 

 

After repair work, surely assemble the disassembled parts, and connect and lead the removed

 

wires as before.

 

Perform the work so that the cabinet or panel does not catch the inner wires.

Assembly/

If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is

Cabling

caused at user’s side.

 

 

 

After the work has finished, be sure to use an insulation tester set (500V Megger) to check the

 

resistance is 2MΩ or more between the charge section and the non-charge metal section

 

(Earth position).

Insulator

If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.

check

 

 

 

 

When the refrigerant gas leaks during work, execute ventilation.

 

If the refrigerant gas touches to a fire, poisonous gas generates.

 

A case of leakage of the refrigerant and the closed room full with gas is dangerous because a

Ventilation

shortage of oxygen occurs. Be sure to execute ventilation.

 

 

 

When the refrigerant gas leaks, find up the leaked position and repair it surely.

 

If the leaked position cannot be found up and the repair work is interrupted, pump-down and

 

tighten the service valve, otherwise the refrigerant gas may leak into the room.

 

The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove

 

though the refrigerant gas itself is innocuous.

 

When installing equipment which includes a large amount of charged refrigerant such as a multi

 

air conditioner in a sub-room, it is necessary that the density does not the limit even if the

 

refrigerant leaks.

 

If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.

 

 

 

Tighten the flare nut with a torque wrench in the specified manner.

Compulsion

Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may

result in refrigerant leakage.

 

 

 

 

Nitrogen gas must be used for the airtight test.

 

 

 

The charge hose must be connected in such a way that it is not slack.

 

 

 

For the installation/moving/reinstallation work, follow to the Installation Manual.

 

If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or

 

fire is caused.

 

 

– 8 –

Page 8
Image 8
Toshiba RAV-SM2802DT-TR, RAV-SM2802DT-E, RAV-SM2242DT-TR service manual Refrigerant used by this air conditioner is the R410A

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.