nWire connection change of fan motor

Concealed Duct High Static Pressure

Installation Manual

nWire connection change of fan motor

This duct is composed of 3 fan motors.

To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number (F1, F2 or F3) terminal.

The wires of the fan motor has been connected to (F2) [External static pressure 137Pa (14mmAq)] as factory default.

Low static pressure (F1)

FM

 

 

 

FM

 

 

 

FM

 

 

 

YEL : Yellow

 

 

 

 

 

 

 

 

 

BLU : Blue

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor

YEL

BLU

ORG

Fan motor

YEL

BLU

ORG

Fan motor

YEL

BLU

ORG

ORG : Orange

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

 

ORG

 

FAN3

ORG

 

FAN2

ORG

 

FAN1

 

Standard (Middle) static pressure (F2)
Fan tap changing terminal block

Concealed Duct High Static Pressure

Installation Manual

6 DRAIN PIPING WORK

Low static pressure (F1) CAUTION

Following the Installation Manual, perform the drain piping work that water is properly drained, and apply a heat insulation not to cause a dew condensation.

Inappropriate piping work may cause the water leakage in the room and wet of furniture.

REQUIREMENT

The drain piping flows the natural drainage. Make sure to set the drain piping from the unit with descending slope of 1/50 to 1/100 and do not make up-down or trap in the midway.

Set the horizontal pulling of the drain pipe to 20m or less. When drain piping is too long, attach the support bracket at intervals of 1.5m to 2m to avoid the pipe becomes undulant as shown in figure below.

<Example for installation of the main piping (Incl. piping support)>

1.5 to 2 m

As long as possible

– 90 –

FM

Fan motor

YEL

 

BLU

ORG

FM

 

 

Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN3

 

 

 

 

 

 

YEL

 

BLU

ORG

FM

 

 

Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN2

 

 

 

 

 

 

YEL

 

BLU

ORG

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN1

 

 

 

 

 

 

Electrical control box

Control

P.C. board Standard (Middle) static pressure (F2)

Fan tap changing terminal block 4P terminal block

3P terminal block

2P terminal block

Up-down bend

Descending slop of

Descending slop of

VP-30

Trap

1/50 to 1/100

1/50 to 1/100

 

 

High static pressure (F3)

FM

YEL

BLU

ORG

FM

YEL BLU

ORG

FM

YEL

BLU

ORG

 

Fan motor

Fan motor

Fan motor

 

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

F1 F2 F3 F4

 

 

 

ORG

FAN3

ORG

FAN2

 

ORG

FAN1

 

 

 

 

 

 

 

 

Terminal block No.

 

Fan motor wiring

External static pressure Pa (mmAq)
Remarks

 

F1

 

 

 

Yellow

 

 

 

69 (7)

 

 

 

 

Low static pressure

 

 

 

 

 

 

 

 

 

 

 

 

F2

 

 

 

Blue

 

 

 

137 (14)

Factory default

 

 

 

Middle static pressure

 

 

 

 

 

 

 

 

 

 

 

F3

 

 

 

Orange

 

 

 

196 (20)

 

 

 

 

High static pressure

 

 

 

 

 

 

 

 

 

 

 

Do not use F4.

NOTE

When the external static pressure is changed, write down the static pressure once change in the wiring diagram of the indoor unit is made.

Be sure to connect the drain pipe to the air conditioner with adhesive to avoid water leakage from the joint portion.

Condensation may occur on the drain pipes including collective pipes.

All drain pipes must be wrapped with heat insulator to prevent dew condensation.

Especially a part where drain pipe is connected to the indoor unit must be firmly insulated with the provided heat insulator.