No.

Item

 

Outline of specifications

 

 

 

 

Remarks

 

 

 

 

 

 

 

3

Room temp.

1)

Adjustment range: Remote controller setup temperature (°C)

 

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

HEAT

 

AUTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired type

 

18 to 29

 

18 to 29

 

18 to 29

 

 

 

 

 

 

 

 

 

 

 

2)

Using the Item code 06, the setup temperature in heating Shift of suction

 

 

 

operation can be corrected.

 

 

 

 

 

 

 

temperature in heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

 

 

Setup data

 

 

0

 

2

 

4

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp. correction

 

+0°C

+2°C

 

+4°C

 

+6°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup air volume operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor formation

 

 

 

 

 

Setup data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-way Air Discharge Cassette Type

 

 

 

 

 

 

 

 

 

 

 

2-way Air Discharge Cassette Type

 

 

 

2

 

 

 

 

 

 

Concealed Duct Standard Type

 

 

 

 

 

 

 

 

 

High Wall Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Under Ceiling Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor Standing Concealed Type

 

 

 

0

 

 

 

 

 

 

Floor Standing Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Automatic

1)

Based on the difference between Ta and Ts, the operation

 

capacity control

 

frequency is instructed to the outdoor unit.

 

 

 

(GA control)

2)

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 90 seconds, the room temperature difference

 

 

 

 

 

between temperature detected by Ta and Ts and the varied

 

 

 

room temperature value are calculated to obtain the

 

 

 

correction value of the frequency command and then the

 

 

 

present frequency command is corrected.

 

 

 

 

 

 

 

 

Ta (n) – Ts (n) : Room temp. difference

 

 

 

 

 

n

: Counts of detection

 

 

 

 

 

 

 

 

Ta (n-1) – Ts (n)

: Varied room temp. value

 

 

 

 

 

n – 1

: Counts of detection of 90 seconds before

 

 

3)

Heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 1 minute (60 sec.), the room temperature

 

 

 

 

 

difference between temperature detected by Ta and Ts

 

 

 

and the varied room temperature value are calculated to

 

 

 

obtain the correction value of the frequency command

 

 

 

and then the present frequency command is corrected.

 

 

 

Ts (n) – Ta (n)

: Room temp. difference

 

 

 

 

 

n

: Counts of detection

 

 

 

 

 

 

 

 

Ta (n) – Ta (n – 1): Varied room temp. value

 

 

 

 

 

n – 1

: Counts of detection of 1 minute before

NOTE)

In case that Low volume is set, the maximum frequency is restricted to approx. [SB].

– 24 –

Page 24
Image 24
Toshiba RAV-SM2802DT-E, RAV-SM2242DT-TR, RAV-SM2802DT-TR service manual Setup data, Indoor formation

RAV-SM2802DT-TR, RAV-SM2242DT-TR, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.