Toshiba RAV-SM2802DT-E, RAV-SM2242DT-TR 57, Function selection item No. DN list, Item, Contents

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 57
Image 57

Function selection item No. (DN) list

DN

Item

 

Contents

At shipment from factory

 

 

 

 

 

 

 

 

0000:None

 

0001: 150H

 

01

Filter sign lighting time

0002:2500H

 

0003: 5000H

According to type

 

 

0004:10000H

 

0005: Clogging sensor used

 

 

 

 

 

 

 

03

Central control address

0001:No.1 unit

to

0064: No.64 unit

0099:Undecided

0099:Undecided

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0000:No shift

 

0001: +1°C

0002:+2°C

06

Heating suction temp. shift

0002:+2°C

to

0010: +10°C

(Floor type 0000: 0°C)

 

 

 

 

(Up to +6 is recommended.)

 

 

 

 

 

10

Type

0000:(1-way air discharge cassette)

According to model type

0001:(4-way air discharge cassette) to 0038

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000:Undecided

 

0001 to 0034

According to capacity type

 

 

 

 

 

 

12

Line address

0001:No.1 unit

to

0030: No.30 unit

0099:Undecided

 

 

 

 

 

 

13

Indoor unit address

0001:No.1 unit

to

0064: No.64 unit

0099:Undecided

 

 

 

 

 

 

14

Group address

0000:Individual

 

0001: Master unit in group

0099:Undecided

0002:Follower unit in group

 

 

 

 

 

 

 

 

 

 

 

 

In automatic cooling/heating, temp.

0000:0 deg

to

0020: 20 deg

 

1E

width of cool heat, heat

(Cool/heat are reversed with ± (Data value) /

0003:3 deg (Ts±1.5)

 

cool mode selection control point

2 against the set temperature)

 

 

 

 

 

 

 

28

Automatic reset of power failure

0000:None

 

0001: Provided

0000:None

 

 

 

 

 

 

 

Selection of option / error input

0000:Filter input

 

 

 

2A

0001:Alarm input (Air cleaner, etc.)

0002:Humidifier

(CN70)

 

0002:Humidifier input

 

 

 

 

 

 

 

 

 

 

 

 

 

2b

Selection of thermostat output

0000:Indoor thermostat ON

 

0000:Thermostat ON

(T10 ƒ )

0001:ON receiving output of outdoor compressor

 

 

 

 

 

 

 

 

31

Fan (Single operation)

0000:Impossible

 

0001: Possible

0000:Impossible

 

 

 

 

 

 

32

Sensor selection

0000: Body TA sensor

 

 

0000:Body sensor

0001: Remote controller sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

0000:No control

 

 

 

40

Humidifier control

0001:Humidifier + Vaporizing type (Pump ON)

0003:Humidifier ON

(+Drain pump control)

0002:Humidifier + Supersonic type

Pump OFF

 

 

(This function is not provided.)

(Pump ON when specified time elapsed)

 

 

 

0003:Humidifier + Natural drain type (Pump OFF)

 

 

 

 

 

 

 

60

Timer setting

0000:Operable

 

 

0000:Operable

(Wired remote controller)

0001:Operation prohibited

 

 

 

 

 

 

 

 

 

 

C2

Current demand X% to outdoor unit

0050:50%

to

0100: 100%

0075:75%

 

 

 

 

 

D0

Existence of remote controller save

0000:Invalid (Impossible)

0001: Valid (Possible)

0001:Valid (Possible)

function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).

– 57 –

Page 57
Image 57
Toshiba RAV-SM2802DT-E, RAV-SM2242DT-TR, RAV-SM2802DT-TR 57, Function selection item No. DN list, Item, Contents