Toshiba RAV-SM2242DT-TR, RAV-SM2802DT-E 31, Function, Connector, Specifications, Remarks

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 31
Image 31

6-3-1. Optional Connector Specifications of Indoor P.C. Board

Function

Connector

Pin

Specifications

Remarks

No.

No.

 

 

 

 

 

 

 

 

 

 

1

DC12V

Setting at shipment: Interlock of ON by indoor unit operation, with

Ventilation output

CN32

 

 

OFF by stop operation

2

Output

The single operation setting by FAN button on the remote controller

 

 

 

 

(Open collector)

is performed on the remote controller (DN [31] = 0000 0001)

 

 

 

 

 

 

 

 

 

 

1

DC12V

 

 

 

 

 

 

 

 

2

Defrost output

ON when outdoor unit is defrosted

 

 

(Open collector)

 

 

 

 

 

 

 

 

 

 

 

3

Thermostat ON output

ON when real thermostat is on. (Compressor ON)

 

 

(Open collector)

 

 

 

 

Option output

CN60

 

 

 

4

Cooling output

ON when operation mode is cooling system

 

 

 

 

(Open collector)

(COOL, Cooling/Heating automatic cooling)

 

 

 

 

 

 

 

 

 

 

5

Heating output

ON when operation mode is heating system

 

 

(Open collector)

(HEAT, Cooling/Heating automatic heating)

 

 

 

 

 

 

 

 

 

 

6

Fan output

ON when indoor fan is on. (When air cleaner is used)

 

 

(Open collector)

OFF while clean operation is performed.

 

 

 

 

 

 

 

 

 

 

1

DC12V

 

Outside error

 

 

 

Generate the warning code “L30” (continuously for 1 minute) and

CN80

2

NC

input

stop the operation forcibly.

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

 

 

1

DC12V

 

 

 

 

 

 

 

 

2

Panel operation input

 

 

 

 

 

The grille is controlled according to up/down operation from the

 

 

 

Panel up output

AUTO up/

 

3

remote controller.

CN20

(Open collector)

down grille ()

 

Setting of automatic up/down grille provided is performed on the

 

 

 

 

 

4

Panel down output

remote controller. (DN [30] = 0000 0001)

 

 

 

 

 

(Open collector)

 

 

 

 

 

 

 

 

 

 

 

 

5

0V

 

 

 

 

 

 

 

 

1

A

Selection of option error input (Protective operation display of device

FILTER

 

attached to outside) or

 

 

 

Humidifier setting input (Vaporizing + Drain pump ON)

Option error /

 

 

 

CN70

 

 

Humidifier is set at shipment from factory.

 

 

Humidifier setting ()

 

 

 

2

0V

Setting of option error input is performed on the remote controller.

 

 

 

 

 

 

(DN [2A] = 0002 0001)

 

 

 

 

 

CHK

 

1

0V

This check is used to check indoor operation.

CN71

 

 

(Performs operation of indoor fan “H”, Louver horizontal and Drain

Operation check

 

 

 

2

 

pump ON without communication with outdoor and remote controller)

 

 

 

 

 

 

 

 

DISP

 

1

0V

 

CN72

 

 

Communication is available by indoor unit and remote controller only.

Exhibition mode

2

Demand input

 

 

 

 

 

 

 

 

 

 

EXCT

 

1

 

 

CN73

 

0V

Indoor unit forced thermostat OFF operation

Demand

2

 

 

 

 

 

 

 

 

 

 

 

 

This option is not provided to oversea models.

– 31 –

Page 31
Image 31
Toshiba RAV-SM2242DT-TR, RAV-SM2802DT-E, RAV-SM2802DT-TR service manual 31, Function, Connector, Specifications, Remarks