Toshiba RAV-SM2802DT-TR, RAV-SM2802DT-E, RAV-SM2242DT-TR service manual E04 error, E10 error, 41

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 41
Image 41
[E04 error]

[E04 error]

NO

Does outdoor operate?

YES

Is group address setup of

NO

 

remote controller correct?

 

 

YES

 

 

 

 

 

NO

Are wiring in indoor unit and

 

1, 2, 3 inter-unit cables correct?

 

 

YES

 

 

 

 

 

 

Check CODE No. [14].

Correct wiring and

inter-unit cables.

Check indoor P.C. board.

Defect Replace

Are wirings of terminal blocks (1, 2, 3) wired to CN67 normal?

YES

Check outdoor P.C. board.

Defect Replace

NO

Correct wiring of connector

and terminal blocks.

[E10 error]

YES

Is there no disorder of power supply?

NO

Check indoor control P.C. board

(MCC-1403).

Defect Replace

Check power supply voltage.

Correct lines.

Check and eliminate noise, etc.

– 41 –