Toshiba RAV-SM2802DT-TR Low static pressure F1, Standard Middle static pressure F2, 20, Remarks

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 20
Image 20
Low static pressure (F1)

nWire connection change of fan motor

This duct is composed of 3 fan motors.

To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number

(F1, F2 or F3) terminal.

The wires of the fan motor has been connected to (F2) [External static pressure 137Pa (14mmAq)] as factory default.

Low static pressure (F1)

FM

FM

 

 

 

 

 

 

 

Fan motor

YEL

BLU

ORG

Fan motor

 

 

 

 

 

 

 

 

 

 

 

YEL

BLU

ORG

FM

Fan motor

YEL

BLU

YEL: Yellow

BLU: Blue

ORG: Orange

ORG

F1 F2 F3 F4

F1 F2 F3 F4

F1 F2 F3 F4

 

 

 

 

 

 

 

ORG

 

 

 

 

 

 

ORG

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN3

 

 

 

 

FAN2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard (Middle) static pressure (F2)

ORG

FAN1

Fan tap changing terminal block

FM

FM

FM

Fan motor

 

ORG

Fan motor

 

ORG

Fan motor

BLU

ORG

YEL

BLU

YEL

BLU

YEL

F1 F2 F3 F4

F1 F2 F3 F4

F1 F2 F3 F4

ORG

 

FAN3

ORG

 

FAN2

ORG

 

FAN1

High static pressure (F3)

FM

FM

FM

Fan motor

 

Fan motor

 

 

ORG

Fan motor

 

 

ORG

YEL

BLU

ORG

YEL

BLU

 

YEL

BLU

F1 F2 F3 F4

F1 F2 F3 F4

F1 F2 F3 F4

 

ORG

FAN3

 

ORG

 

FAN2

 

ORG

FAN1

 

 

 

 

 

 

 

Electrical control box

Control

P.C. board Standard (Middle) static pressure (F2)

4P terminal block

3P terminal

2P terminal block block

Terminal block No.

Fan motor wiring

External static pressure

Remarks

Pa (mmAq)

 

 

 

 

 

 

 

 

F1

Yellow

69

(7)

 

Low static pressure

 

 

 

 

 

 

 

 

 

 

F2

Blue

137

(14)

Factory default

Middle static pressure

 

 

 

 

 

 

 

 

 

F3

Orange

196

(20)

 

High static pressure

 

 

 

 

 

 

 

 

 

 

Do not use F4.

NOTE

When the external static pressure is changed, write down the static pressure once change in the wiring diagram of the indoor unit is made.