Toshiba RAV-SM2242DT-TR, RAV-SM2802DT-E service manual Item, Outline of specifications, Remarks

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 28
Image 28
<In case of wired remote controller>

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

12

Frequency fixed

<In case of wired remote controller>

Approx. command

 

operation

1)

When pushing [CHK] button for 4 seconds or more,

frequency [S7]

 

(Test run)

 

 

 

[TEST] is displayed on the display screen and the

 

 

 

 

mode enters in Test run mode.

 

 

 

2)

Push [ON/OFF] button.

 

 

 

3)

Using [MODE] button, set the mode to [COOL] or

 

 

 

 

[HEAT].

 

 

 

 

• Do not use other mode than [COOL]/[HEAT]

 

 

 

 

mode.

 

 

 

 

• During test run operation, the temperature cannot

 

 

 

 

be adjusted.

 

 

 

 

• An error is detected as usual.

 

 

 

 

• A frequency fixed operation is performed.

 

 

 

4)

After the test run, push [ON/OFF] button to stop the

 

 

 

 

operation. (Display in the display part is same as the

 

 

 

 

procedure in Item 1.)

 

 

 

5)

Push [CHK] button to clear the test run mode.

 

 

 

 

([TEST] display in the display part disappears and

 

 

 

 

the status returns to the normal stop status.)

 

 

 

 

 

 

13

Filter sign display

1)

The operation time of the indoor fan is calculated,

[FILTER ] goes on.

 

 

 

the filter reset signal is sent to the remote controller

Specified time

 

 

 

when the specified time has passed, and it is

 

 

 

displayed on LCD.

Duct: 2500H

 

 

2)

When the filter reset signal has been received from

 

 

 

 

the remote controller, time of the calculation timer

 

 

 

 

is cleared.

 

 

 

 

In this case, the measurement time is reset if the

 

 

 

 

specified time has passed, and display on LCD

 

 

 

 

disappears.

 

14 Central control mode

1)

Setting at the centerl controller side enables to

 

 

 

 

 

selection

 

select the contents which can be operated on the

 

 

 

 

 

 

 

remote controller at indoor unit side.

 

 

 

 

 

 

2)

Setup contents

 

 

 

 

 

 

 

• 64 line central controller (TCB-SC642TLE2)

Display at remote

 

 

[Individual]: Operated on the remote controller

controller side

 

 

(Priority to second pushing)

(No display)

 

 

 

[Central 1]: ON/OFF operation cannot be

[Central

] goes on

 

 

operated on the remote controller.

 

 

 

 

 

 

 

[Central 2]: ON/OFF, mode selection, temp. setup

[Central

] goes on

 

 

operations cannot be operated on

 

 

 

 

 

 

 

the remote controller.

 

 

 

 

 

 

 

[Central 3]: Mode selection and temp. setup

[Central

] goes on

 

 

operations cannot be operated on the

 

 

 

 

 

 

 

remote controller.

 

 

 

 

 

 

 

[Central 4]: Mode selection cannot be operated

[Central

 

 

] goes on

 

 

on the remote controller.

“Fixed with 75%”.)

In case of the wireless type, the display lamp does not change but the contents are same.

If operating an item which is prohibited by the central control mode from the remote controller, it is notified with the receive sound, Pi, Pi, Pi, Pi, Pi (5 times).

– 28 –

Page 28
Image 28
Toshiba RAV-SM2242DT-TR, RAV-SM2802DT-E Item, Outline of specifications, Remarks, <In case of wired remote controller>