Toshiba RAV-SM2802DT-E service manual Wiring specifications, 5. P.C. board switch SW01 setup, 63

Models: RAV-SM2802DT-TR RAV-SM2242DT-TR RAV-SM2802DT-E

1 110
Download 110 pages 30.72 Kb
Page 63
Image 63
4.Wiring specifications

4.Wiring specifications

Use 2-core with no polar wire.

Match the length of wire to wire length of the central control system.

If mixed in the SMMS system, the wire length is lengthened with all indoor/outdoor inter-unit wire length at side.

To prevent noise trouble, use 2-core shield wire.

No. of wires

Size

2Up to 1000m: twisted wire 1.25mm2

Up to 2000m: twisted wire 2.0mm2

Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter (DI, SDI) unit setup)

CAUTION

Central control device U1 U2

1)Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)

2)Apply open process to the last terminal (insulating process).

3)Ground earth wire to 1 point at indoor unit side.

5. P.C. board switch (SW01) setup Caution 2

Outdoor unit

1

2

3

Caution 1

1 2 3

Central control system wiring

1 2 3

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

U3 U4

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

Remote controller

 

 

 

 

Header

 

 

 

 

 

 

 

Follower

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

U3

U4

 

1

 

2

3

 

 

 

U3

U4

 

1

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

A B

Remote controller

Remote controller

(Group operation)

– 63 –Manual background : 1:1 model connection interface (This option)

5. P.C. board switch (SW01) setup

When performing collective control by DI or SDI only, the setup of terminator is necessary.

Using SW01, set up the terminator.

Set up the terminator to only the adapter connected to the indoor unit of least line address No.

Central control device

 

U1

U2

 

 

U3

U4

 

Central control device

 

U1

U2

 

 

U3

U4

 

Central control devices: Max. 10 units

Refrigerant line 1

Outdoor unit

1 2 3

Indoor unit

 

U3 U4

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

1:1 model connection interface ( This product ) sold separately

Remote controller

Refrigerant line 2

Central control

1

2

3

 

 

 

system wiring

 

 

 

 

 

 

Header

 

 

 

unit

U3 U4

1

2

3

A B

Remote controller

Refrigerant line 3

1 2 3

Indoor/outdoor inter-unit wire (AC230V serial)

Follower unit

1 2 3

A B

Remote controller wiring

Remote controller

 

 

 

 

 

 

Group operation (Max. 8 units)

 

 

 

 

 

 

 

 

Line address

 

1

 

 

 

2

 

SW01 Bit 1

 

ON

 

 

OF

(OFF at shipment from factory)

SW01 Bit 2

 

OFF

 

 

OFF

(OFF at shipment from factory)

Remarks

Turn SW01 Bit 1 to ON.

 

As status shipped from factory

 

(Reference) Setup contents of switch

 

 

 

 

 

 

 

 

 

 

SW01

 

Terminator

 

Remarks

Bit 1

Bit 1

 

 

 

 

 

 

 

 

OFF

OFF

 

None

 

Mixed with multi (Link wiring) at shipment from factory

ON

OFF

 

100Ω

 

Central control by digital inverter only

OFF

ON

 

75Ω

 

Spare

 

ON

ON

 

43Ω

 

Spare

 

– 63 –

Page 63
Image 63