Specifications

Table 1.5 Specifications for 60 V to 600 V Models

Models

60-46

100-28

150-18

300-9

600-4

Output Ratings:

 

 

 

 

 

Output Voltage 1

0-60 V

0-100 V

0-150 V

0-300 V

0-600 V

Output Current 2

0-46 A

0-28 A

0-18 A

0-9 A

0-4 A

Output Power

2760 W

2800 W

2700 W

2700 W

2400 W

Line Regulation: 3

 

 

 

 

 

Voltage (0.01% of Vmax + 2 mV)

8 mV

12 mV

1 7mV

32 mV

62 mV

Current (0.01% of Imax + 2 mA)

6.6 mA

4.8 mA

3.8 mA

2.9 mA

2.4 mA

Load Regulation: 4

 

 

 

 

 

Voltage (0.02% of Vmax + 5 mV)

17 mV

27 mV

35 mV

65 mV

125 mV

Current (0.02% of Imax + 5 mA)

14.2 mA

10.6 mA

8.6 mA

6.8 mA

5.8 mA

Meter Accuracy:

 

 

 

 

 

Voltage (1% of Vmax + 1 count)

0.7 V

1.1 V

1.6 V

4 V

7 V

Current (1% of Imax + 1 count)

0.56 A

0.38 A

0.19 A

0.1 A

0.05 A

Output Noise (0-20 MHz):Voltage (p-p)

150 mV

175 mV

200 mV

400 mV

500 mV

 

 

 

 

 

 

Output Ripple (rms):

 

 

 

 

 

Voltage

15 mV

25 mV

25 mV

40 mV

100 mV

Current 5

100 mA

80 mA

40 mA

20 mA

10 mA

Drift (30 minutes): 6

 

 

 

 

 

Voltage (0.05% of Vmax)

30 mV

50m V

75 mV

150 mV

300 mV

Current (0.7% of Imax)

322 mA

196m A

126 mA

63 mA

28 mA

For Resistive Programming:

 

 

 

 

 

Voltage (0.6% of Vmax)

360 mV

600 mV

900 mV

1800 mV

3600 mV

Current (0.6% of Imax)

276 mA

168 mA

108 mA

54 mA

24 mA

Drift (8 hours): 7

 

 

 

 

 

Voltage (0.05% of Vmax)

30 mV

50 mV

75 mV

150 mV

300 mV

Current (0.05% of Imax)

23 mA

14 mA

9 mA

4.5 mA

2 mA

For Resistive Programming:

 

 

 

 

 

Voltage (0.3% of Vmax)

180 mV

300 mV

450 mV

900 mV

1800 mV

Current (0.3% of Imax)

138 mA

84 mA

54 mA

27 mA

12 mA

Temperature Coefficient: 8

 

 

 

 

 

Voltage (0.02% of Vmax/°C)

12 mV

20 mV

30 mV

60 mV

120 mV

Current (0.03% of Imax/°C)

13.8 mA

8.4 mA

5.4 mA

2.7 mA

1.2 mA

For Resistive Programming:

 

 

 

 

 

Voltage (0.06% of Vmax/°C)

36 mV

60 mV

90 mV

180 mV

360 mV

Current (0.06% of Imax/°C)

28 mA

16.8 mA

10.8 mA

5.4 mA

2.4 mA

OVP Adjustment Range:

 

 

 

 

 

(5% to 110% of Vmax)

3-66 V

5-110 V

7.5-165 V

15-330 V

30-660 V

Efficiency: 9

0.90

0.90

0.90

0.91

0.91

28