Xantrex Technology XFR 2800 manual Strip the ends of the wires

Models: XFR 2800

1 90
Download 90 pages 12.58 Kb
Page 50
Image 50
1.Strip the ends of the wires.

Installation

Load Connection

7.5V to 100 V Models The 7.5 V to 100 V models are equipped with output bus bars. To make a typical load connection to a 7.5 V, 300 A power supply:

1.Strip the ends of the wires.

2.Remove the top part of the output cover. Do not remove the chassis-mounted part of the cover.

3.Loosen wire clamp screws (part of strain relief). Do not disassemble the strain relief.

4.Insert load wire in strain relief.

5.Install connectors to load wiring.

6.Fasten connectors to bus bars with 5/16 in. x 5/8 in. (M8 x 16 mm) screws, 5/16 in. (M8) flat washers, lock washers, and hex nuts as shown in Figure 2.5.

7.Tighten the strain relief clamp.

8.Replace the top cover.

Note: Bus bar hole sizes are one of 0.343 in. (8.7 mm) D; two of 0.197 in. (5.0 mm) D.

Manual background Hex Nut (2 places)

Lock Washer (2 places)

Flat Washer (2 places)

Screw (2 places)

Wire connector (2 places)

Assembled View

Figure 2.5 Typical Load Connection Hardware

(For 7.5 V to 100 V models.)