Xantrex Technology XFR 2800 manual Input Conditions, Based on 100 V, 28 A model

Models: XFR 2800

1 90
Download 90 pages 12.58 Kb
Page 32
Image 32
Additional

Features and Specifications

Specifications

Additional

Specifications

Rise Time (No Load, Full Load): 1

7.5 V to 60 V models: 100 ms;

 

100 V to 600 V models: 170 ms

 

 

Fall Time (No Load): 1

4 s

Fall Time (Full Load): 1

7.5 V to 60 V models: 100 ms;

 

100 V to 600 V models: 170 ms

 

 

Voltage Mode Transient Response:2

<3 ms

Time Delay from power on until

7 s maximum

output stable

 

1.Measured with stepped 0-10 V analog programming source and a resistive load.

2.Time for the output voltage to recover within 0.5% of its rated value after a step change in load current of 10% to 90% of rated output with an output setpoint between 50-100% of rated value. Load slew rate <6 A/ms.

Input

Conditions

Rated AC Input Voltage

200/208/220/230/240 Vac (nominal)

 

Maximum AC Input Power

5000 VA

 

 

Operational AC Input Voltage

190-264 Vac, 1φ (24.3 A maximum at 208 Vac;

 

 

 

22.4 A maximum at 230 Vac.)

 

 

 

Auto range select function.

 

Input Frequency Range

47-63 Hz

 

 

Power Factor

0.65 typical

 

 

I

30

 

100% at 190 Vac

O

N

 

 

U

P

25

 

 

T

U

 

 

 

P

T

20

 

100% at 264 Vac

U

C

 

 

 

T

 

 

50% at 190 Vac

C

U

15

 

R

 

 

50% at 264 Vac

U

R

10

 

R

E

 

 

R

N

 

 

 

E

5

 

 

N

T

 

 

(A)

 

 

 

T

 

 

 

 

 

0

50%

100%

 

 

 

 

 

OUTPUT VOLTAGE

 

 

Figure 1.5 Typical Input Current Characteristics

(Based on 100 V, 28 A model.)

30

Operating Manual for XFR 2.8kW Series Power Supply

Page 32
Image 32
Xantrex Technology XFR 2800 manual Input Conditions, Based on 100 V, 28 A model, Additional Specifications