PREINSTALLATION

Environmental/electrical requirements

Your DocuPrint 96/DocuPrint 96MX LPS has important environmental and electrical requirements that must be accommodated. These requirements are summarized in the table below. For further details on electrical requirements, refer to the following voltage charts and wiring diagrams.

Table 3-6.DocuPrint 96/DocuPrint 96MX Environmental and

 

electrical requirements

 

 

 

Environmental requirements

 

 

 

 

 

Operating temperature

Recommended:

72° F ± 4° F/22° C ± 2° C

 

Minimum:

60° F/15.5° C

 

Maximum:

80° F/29.5° C

 

 

 

Humidity

Recommended: 4

45% ± 10%

 

Minimum:

15%

 

Maximum:

85%

 

 

 

Altitude

Normal:

Up to 6,000 feet/1830 m above sea level

 

Maximum:

9,000 feet/2743 m above sea level

 

 

 

Heat dissipation

 

 

 

 

 

System controller

Operating:

4,354 Btu per hour

 

Standby:

2,485 Btu per hour

 

 

 

Peripheral cabinet (fully configured)

Operating:

3,195 Btu per hour

 

Standby:

1,775 Btu per hour

 

 

 

Printer

Operating:

28,140 Btu per hour

 

Standby:

4,454 Btu per hour

 

 

 

System controller

U.S. and Canada, 60

208/240 VAC (1 phase) or 208/220 VAC

 

Hz:

(2 phase)

 

 

15 amp service

 

 

NEMA 6-15R or ANSI C73, 20R

 

 

KVA 1.1 (operating)

 

International, 50 Hz:

200/240 VAC +/-10%

 

 

15 amp service;

 

 

Power connector per local codes

 

 

 

3-16

XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE

Page 46
Image 46
Xerox 721P85600 manual Environmental/electrical requirements