PREINSTALLATION

50 Hz DELTA printer outlet voltages

Note: All power outlets must be dedicated only to this equipment.

Ensure that each power cord has a separate circuit.

50 Hz DELTA configurations only: Measure the DELTA connection voltages at the power source. The required voltages are shown in table 3-11.

Consult with your service representative to determine the type of plug and receptacle to be used for your 50 Hz printer.

Table 3-11.Printer (50 Hz only) DELTA connection for 220/230/ 240 V Service outlet

Service outlet

 

 

 

configuration

Measurement

Nominal

Range

 

 

 

 

4 Wire 220 V

Line 1 to Line 2

220 V RMS

198-242 V RMS

 

 

 

 

4 Wire 220 V

Line 2 to Line 3

220 V RMS

198-242 V RMS

 

 

 

 

4 Wire 220 V

Line 1 to Line 3

220 V RMS

198-242 V RMS

 

 

 

 

4 Wire 230 V

Line 1 to line 2

230 V RMS

207-253 V RMS

 

 

 

 

4 Wire 230 V

Line 2 to line 3

230 V RMS

207-253 V RMS

 

 

 

 

4 Wire 230 V

Line 1 to line 3

230 V RMS

207-253 V RMS

 

 

 

 

4 Wire 240 V

Line 1 to Line 2

240 V RMS

216-264 V RMS

 

 

 

 

4 Wire 240 V

Line 2 to Line 3

240 V RMS

216-264 V RMS

 

 

 

 

4 Wire 240 V

Line 1 to Line 3

240 V RMS

216-264 V RMS

 

 

 

 

3-20

XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE

Page 50
Image 50
Xerox 721P85600 manual Hz Delta printer outlet voltages