PREINSTALLATION

50 Hz system controller and peripheral cabinet power cord configurations

Figure 3-11 shows the 50 Hz system controller power cord configuration.

Figure 3-11.System controller and peripheral cabinet power cord 50 Hz installation 200/230 VAC, single phase, 15A

Note: The 50 Hz plug and receptacle specifications vary according to local codes.

60 Hz printer outlet voltages

Note: All power outlets must have a dedicated circuit for each system equipment piece. Ensure that each power cord has a separate circuit.

Refer to table 3-12 for the 60Hz voltage requirements at the power outlet.

Table 3-12.Printer (50 Hz) voltage requirements at power outlet

Service outlet

 

 

 

configuration

Measurement

Nominal

Range

 

 

 

 

4 Wire

Line 1 to Neutral

120 V RMS

107-127 V RMS

 

 

 

 

4 Wire

Line 2 to Neutral

120 V RMS

107-127 V RMS

 

 

 

 

4 Wire

Neutral to

0 V RMS

0-10 V RMS

 

Ground

 

 

 

 

 

 

4 Wire

Line 1 to Line 2

208 V RMS

182-220 V RMS

 

 

 

 

 

Line 1 to Line 2

240 V RMS

210-254 V RMS

 

 

 

 