Therefore:

Therefore:

(100%) (50% x 200) = 100A = Vanes stop open- ing

(104%) (50% x 200) = 104A = Vanes driven to- ward close position.

SYSTEM RUN – AUTO VANES

Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode, and the vanes are operating in AUTO mode.

SYSTEM RUN – VANES OPENING

Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode with:

The vanes operating in AUTO mode and opening to maintain the leaving chilled water temperature setpoint.

or –

The operator has pressed the vanes OPEN key on the keypad.

SYSTEM RUN – VANES CLOSING

Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode with:

The vanes operating in AUTO mode and closing to maintain the leaving chilled water temperature setpoint.

or –

The operator has pressed the vanes CLOSE key on the keypad.

SYSTEM RUN - VANES HOLDING

Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode, and the operator has pressed the vanes HOLD key.

SYS READY TO START – VANES OPENING

Displayed when the chiller is running and the operator has pressed the vanes OPEN key on the keypad.

SYS READY TO START – VANES CLOSING

Displayed when the chiller is not running and the op- erator has pressed the vanes CLOSE key on the key- pad.

FORM 160.49-O2

SYS READY TO START – VANES HOLDING

Displayed when the chiller is running and the operator has pressed the vanes HOLD key on the keypad.

SYSTEM RUN – LEVEL VALVE OPENING

Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form 160.49-M3 and operating in SERVICE mode. Indicates an “OPEN” command is being output to the variable orifice. Manual level control should be selected only by a qualified service technician.

SYSTEM RUN – LEVEL VALVE CLOSING

Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form 160.49-M3 and operating in SERVICE mode. Indicates a “CLOSE” command is being output to the variable orifice. Manual level control should be selected only by a qualified service technician.

SYSTEM RUN – AUTO LEVEL CONTROL

Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form 160.49-M3 and operating in SERVICE mode. Indicates that neither a “CLOSE” nor “OPEN” command is being output to the variable orifice but is in “AUTO” mode. Manual level control should be selected only by a quali- fied service technician.

SYSTEM RUN – LOW PRESSURE LIMIT IN EFFECT

Displayed when the chiller is running and the evapora- tor pressure falls to 56.2 PSIG (R-22); 27 PSIG (R- 134a). Simultaneously, the pre-rotation vanes will be prevented from further opening. This action maintains chiller operation to prevent low-evaporator-pressure shutdown at 54.3 PSIG (R-22); 25 PSIG (R-134a). When the evaporator pressure rises to 57.5 PSIG (R- 22); 28 PSIG (R-134a), the vanes will be permitted to open. Low pressure limit feature is not used when pro- gram jumper (JP3) is cut (Brine application).

SYSTEM RUN – HIGH PRESSURE LIMIT IN EFFECT

Displayed when the chiller is running and the condenser pressure rises to 246.3 PSIG (R-22); 162.5 PSIG (R- 134a). Simultaneously, the pre-rotation vanes will be inhibited from further opening. This action occurs to prevent system shutdown on high condenser pressure

YORK INTERNATIONAL

23

Page 23
Image 23
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Therefore

FAQ

What does the 'VANES HOLDING' message mean?

The 'VANES HOLDING' message is displayed when the chiller is running and the operator has pressed the vanes HOLD key on the keypad.

When is the 'LOW PRESSURE LIMIT IN EFFECT' message displayed?

The 'LOW PRESSURE LIMIT IN EFFECT' message is displayed when the chiller is running and the evaporator pressure falls to a certain level.

What action occurs when the 'HIGH PRESSURE LIMIT IN EFFECT' message is displayed?

When the 'HIGH PRESSURE LIMIT IN EFFECT' message is displayed, the pre-rotation vanes are inhibited from further opening to prevent system shutdown.