Therefore:
(100%) (50% x 200) = 100A = Vanes stop open- ing
(104%) (50% x 200) = 104A = Vanes driven to- ward close position.
SYSTEM RUN – AUTO VANES
Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode, and the vanes are operating in AUTO mode.
SYSTEM RUN – VANES OPENING
Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode with:
•The vanes operating in AUTO mode and opening to maintain the leaving chilled water temperature setpoint.
–or –
•The operator has pressed the vanes OPEN key on the keypad.
SYSTEM RUN – VANES CLOSING
Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode with:
•The vanes operating in AUTO mode and closing to maintain the leaving chilled water temperature setpoint.
–or –
•The operator has pressed the vanes CLOSE key on the keypad.
SYSTEM RUN - VANES HOLDING
Displayed when the chiller is running, the MicroCom- puter Control Center is in SERVICE mode, and the operator has pressed the vanes HOLD key.
SYS READY TO START – VANES OPENING
Displayed when the chiller is running and the operator has pressed the vanes OPEN key on the keypad.
SYS READY TO START – VANES CLOSING
Displayed when the chiller is not running and the op- erator has pressed the vanes CLOSE key on the key- pad.
FORM
SYS READY TO START – VANES HOLDING
Displayed when the chiller is running and the operator has pressed the vanes HOLD key on the keypad.
SYSTEM RUN – LEVEL VALVE OPENING
Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form
SYSTEM RUN – LEVEL VALVE CLOSING
Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form
SYSTEM RUN – AUTO LEVEL CONTROL
Displayed as a foreground message when manual re- frigerant level control has been selected using the “Spe- cial Setpoints Procedure” in Service manual, Form
SYSTEM RUN – LOW PRESSURE LIMIT IN EFFECT
Displayed when the chiller is running and the evapora- tor pressure falls to 56.2 PSIG
SYSTEM RUN – HIGH PRESSURE LIMIT IN EFFECT
Displayed when the chiller is running and the condenser pressure rises to 246.3 PSIG
YORK INTERNATIONAL | 23 |