period. EPROM version C.02F(T).12 or later pro- vides a 10 minute coastdown period. The compres- sor, condenser water, and cooling tower fans will stop automatically. The oil pump will continue to run for coastdown period. The oil pump will then stop automatically. Once stopped, the
display will be replaced by
SYSTEM READY TO START .
2.Stop the chilled water pump (if not wired into the MicroComputer Control Center, in which case it will shut off automatically simultaneously with the oil pump.) (The actual water pump contact operation is dependent upon the postion of Micro Board jumper J54.)
3.Open the switch to the cooling tower fan motors, if used.
4.The compressor sump oil heater (thermostatically controlled) is energized when the unit is stopped.
PROLONGED SHUTDOWN
If the chiller is to be shut down for an extended period of time (for example, over the winter season), the fol- lowing paragraphs outline the procedure to be followed.
1.Test all system joints for refrigerant leaks with a leak detector. If any leaks are found, they should be repaired before allowing the system to stand for a long period of time.
During long idle periods, the tightness of the sys- tem should be checked periodically.
2.If freezing temperatures are encountered while the system is idle, carefully drain the cooling water from
the cooling tower, condenser, condenser pump, and the chilled water
Open the drains on the cooler and condenser liquid heads to assure complete drainage. (If a Variable Speed Drive, drain its water cooling system. If Solid State Starter. drain water from starter cooling loop.)
3.Move jumper
4.Open the main disconnect switches to the com- pressor motor, condenser water pump and the chilled water pump. Open the 115 volt circuit to the Control Center.
START-UP AFTER PROLONGED SHUTDOWN
1.When putting the system into operation after pro- longed shutdown (during the winter), remove all oil from the compressor. Install a new filter element and charge compressor with fresh oil. Move jumper
2.Operate the Oil Pump (press and release the MAN- UAL OIL PUMP key) until steady oil pressure is established. Then press and release the OIL PUMP key to stop operation of the oil pump. If the water systems were drained, fill the condenser water cir- cuit and chilled liquid circuit.