FORM
To enter CHILLED LIQUID TEMP Setpoint: (Refer to
Fig. 6.)
1.Press and release CHILLED LIQUID TEMP setpoint key. The following program prompt message will be displayed:
LEAVING SETPOINT = XX.X °F (BASE)
(BASE) refers to the base or lowest setpoint avail- able to an Energy Management System. If any En- ergy Management System is applied, this value must be entered into the Energy Management System. Refer to previous explanation or REMOTE/RESET TEMP RANGE, page 11.
2. Use ENTRY keys to enter desired value.
LD00955
3. Press and release ENTER key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
FIG. 6 – KEYPAD – PROGRAMMING “LEAVING CHILLED WATER TEMP” SETPOINT
To Enter % CURRENT LIMIT Setpoint:
(Electro-Mechanical Starter, refer to Fig. 7)
1.Press and release % CURRENT LIMIT setpoint key. The following program prompt message is displayed:
CURRENT LIMIT = XXX% FLA
2.Use ENTRY keys to enter desired value.
3.Press and release ENTER key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
(Solid State Starter, refer to Fig. 7)
1.Press and release % CURRENT LIMIT setpoint key. The following program prompt message is displayed:
CURRENT LIMIT = XXX% FLA; MTR CUR = _ _ _ FLA
2.Use ENTRY keys to enter desired value.
NOTE: Motor Current FLA value is entered by YORK factory and checked at system
3. Press and release ENTER key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
LD00956
FIG. 7 – KEYPAD – PROGRAMMING “% CURRENT LIMIT” SETPOINT
YORK INTERNATIONAL | 15 |