York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 Solid State Starter, refer to Fig

Models: YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 YK M3 M3 G4

1 60
Download 60 pages 33.73 Kb
Page 15
Image 15
(Electro-Mechanical Starter, refer to Fig. 7)

FORM 160.49-O2

To enter CHILLED LIQUID TEMP Setpoint: (Refer to

Fig. 6.)

1.Press and release CHILLED LIQUID TEMP setpoint key. The following program prompt message will be displayed:

LEAVING SETPOINT = XX.X °F (BASE)

(BASE) refers to the base or lowest setpoint avail- able to an Energy Management System. If any En- ergy Management System is applied, this value must be entered into the Energy Management System. Refer to previous explanation or REMOTE/RESET TEMP RANGE, page 11.

2. Use ENTRY keys to enter desired value.

LD00955

3. Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

FIG. 6 – KEYPAD – PROGRAMMING “LEAVING CHILLED WATER TEMP” SETPOINT

To Enter % CURRENT LIMIT Setpoint:

(Electro-Mechanical Starter, refer to Fig. 7)

1.Press and release % CURRENT LIMIT setpoint key. The following program prompt message is displayed:

CURRENT LIMIT = XXX% FLA

2.Use ENTRY keys to enter desired value.

3.Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

(Solid State Starter, refer to Fig. 7)

1.Press and release % CURRENT LIMIT setpoint key. The following program prompt message is displayed:

CURRENT LIMIT = XXX% FLA; MTR CUR = _ _ _ FLA

2.Use ENTRY keys to enter desired value.

NOTE: Motor Current FLA value is entered by YORK factory and checked at system start-up. It cannot be changed without special access code. (Note to service technician: refer to “Programming Instructions” in Service in- struction, Form 160.49-M3.

3. Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

LD00956

FIG. 7 – KEYPAD – PROGRAMMING “% CURRENT LIMIT” SETPOINT

YORK INTERNATIONAL

15

Page 15
Image 15
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Electro-MechanicalStarter, refer to Fig

FAQ

How do I set the CHILLED LIQUID TEMP Setpoint?

To set the CHILLED LIQUID TEMP Setpoint, refer to Fig.6.1 in the official manual and follow the programming instructions provided.

Can I change the Motor Current FLA value for Solid State Starter?

No, the Motor Current FLA value is entered by YORK factory and cannot be changed without special access code.

Where can I find the Programming Instructions for Solid State Starter?

For Programming Instructions for Solid State Starter, refer to Service Instruction Form 160.49-M3.